background image

10

5.4  Position of the decimal point:   ‘dP’

A dummy decimal point can be positioned between
any of the digits or it may be absent.  To position
the decimal point select 'dP' from the menu and
press 

P

.   The decimal point can be moved by

pressing the 

 or 

 push-button.  If a decimal

point is not required it should be positioned beyond
the most or least significant digit.   When
positioned as required press the 

E

 button to enter

the selection and return to the configuration menu.

5.5  Calibration using an external
        current source:   ‘CAL’

This function enables the zero and span of the
indicator to be adjusted using an external
calibrated current source.  When used with an
accurate traceable current source this is the
preferred method of calibration.

Zero is the indicator display with 4mA input
Span is the indicator display with 20mA input

To calibrate the indicator select 'CAL' from the
configuration menu and press 

P

.

  The indicator will

display 'ZEro'  which is a request for a 4mA input
current.  Adjust the external current calibrator to
4.000mA and again press 

P

 

which will reveal the

current zero display.   The flashing digit of the
indicator display can be changed by pressing the

 or 

 buttons, when set as required pressing 

P

will transfer control to the next digit.  When all the
digits have been adjusted, press 

E

 to enter the

new zero and return to the 'ZEro' prompt .

Pressing the 

 button will cause the indicator to

display 'SPAn' which is a request for a 20mA input
current.  Adjust the external current calibrator to
20.000mA and again press 

P

 

which will reveal the

existing span display.   The flashing digit of the
indicator display can be changed by pressing the

 or 

 buttons, when set s required pressing 

P

will transfer control to the next digit.  When all the
digits have been adjusted press 

E

 t

o enter the new

span and return to the 'SPAn' prompt.  Finally
press 

E

 

again to return to the configuration menu.

Notes:

a. The indicator input current must be adjusted to

the required value before the zero and span
functions are entered by pressing the 

 button.

b.  Indicators may be calibrated at currents other

than 4 and 20mA, withiin the range 3.8 to
21.0mA providing the difference between the
two currents is greater than 4mA.  If these
conditions are not complied with, the indicator
displays ‘FaiL’ and aborts the calibration.

c.  If the zero current is greater than the span

current the instrument will be reverse acting
i.e. an increasing input current will cause the
display to decrease.

5

.6  Calibration using internal reference:   ‘SEt’

Using the ‘SEt’ function the indicator can be
calibrated without the need to know the value of
the 4/20mA input current, or to disconnect the
indicator from the 4/20mA loop.

When using the ‘Set’ function the indicator’s
internal reference is used to simulate a 4mA and
20mA input current.

Zero is the display with a simulated 4mA input
Span is the display with a simulated 20mA input

To calibrate the indicator display select 'SEt' from
the configuration menu and press

 

P

.  

The indicator

will display 'ZEro', pressing 

P

 again will reveal the

current display at 4mA.   The flashing digit can be
adjusted by pressing the 

 or 

 buttons,   when

the flashing digit is correct pressing 

P

 

will transfer

control to the next digit.  When all the digits have
been adjusted, press 

E

 to return to the 'ZEro'

prompt.

To adjust the display at 20mA, press the 

 button

which will cause the indicator to display 'SPAn',
pressing 

P

 

will then reveal the indicator’s existing

display at 20mA.   The flashing digit can be
adjusted by pressing the 

 or 

 buttons, when

the flashing digit is correct pressing 

P

 will transfer

control to the next digit.  When all the digits have
been adjusted press 

E

  t

o return to the 'SPAn'

prompt followed by 

E

 to return to the ‘SEt’ prompt

in the configuration menu.

5.7  Bargraph format and calibration:   ‘bAr’
       

Only the BA524E has a bargraph

In addition to a five digit numerical display the
BA524E has a 31 segment analogue bargraph
which may be configured to start and finish
anywhere within the indicator’s numerical display
range.

To configure the bargraph select 'bAr' from the
configuration menu and press

 

P

.  

The indicator will

display 'tYPE', pressing 

P

 again will reveal the

existing bargraph justification which can be
changed to one of the following four or five options
using the 

 or 

 button:

                       

Bargraph justification starts from

‘LEFt’

Left end of display

‘CEntr’

Centre of display

‘riGHT’

Right end of display

‘AlrSP’

Only with alarms – see section 8.3

‘oFF’

Bargraph disabled

When set as required press 

E

 to return to the

‘tYPE’ sub-function prompt.

Summary of Contents for BA504E

Page 1: ...Issue 2 14th December 2011 BA504E BA524E General Purpose loop powered field mounting indicators Issue 2...

Page 2: ...ver range 6 5 Lineariser default configuration 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Custom...

Page 3: ...e g temperature flow pressure or level The BA504E and BA524E are not certified for use in explosive atmospheres For hazardous area application the BA304E BA304NE BA324E or the BA324NE should be used 2...

Page 4: ...indicator and the ACSP access setpoints in display mode function has been enabled P E Provides access to the configuration menu via optional security code Note BA524E only If the indicator has been c...

Page 5: ...ally joined and may be used for linking cable screens The indicator s earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to an earthed post or structure the...

Page 6: ...EMC Both instruments compy with the requirements of the European EMC Directive 2004 108 EC For specified immunity all wiring should be in screened twisted pairs with the screens connected at one poin...

Page 7: ...tion Default Configuration BA504E BA524E Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph...

Page 8: ...8...

Page 9: ...n 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pre...

Page 10: ...etween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the...

Page 11: ...n and oFF When set as required press E to return to the tARE prompt in the configuration menu 5 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit secur...

Page 12: ...r volumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break point required should f...

Page 13: ...13...

Page 14: ...dd a break point Adds a new break point before the displayed break point The calibration of existing break points is not changed but the identification number of all subsequent break point is increase...

Page 15: ...tor display at the first break point When set as required press E to return to the 0 n prompt from which the the next break point can be selected using the or buttons When the required break point has...

Page 16: ...If this does not reveal the cause of the fault it is recommended that the instrument is replaced This can be done without disconnecting power but while the indicator is disconnected the 4 20mA loop w...

Page 17: ...n Both indicators can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9...

Page 18: ...polarised and current will only flow in one direction Ron less than 5 0 7V Roff greater than 1M Fig 10 Equivalent circuit of each alarm output The solid state output of each alarm may be used to switc...

Page 19: ...19...

Page 20: ...setpoint The alarm is activated when the indicator display equals the setpoint See section 8 3 4 Hi Lo Alarm function Defines the alarm function as High or Low See section 8 3 5 no nC Normally open or...

Page 21: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 22: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 23: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 14 Fig 14 Displayed value and setpoints on bargra...

Page 24: ...cting it in series with the indicator s 4 20mA input as shown in Fig 16 which increases the maximum indicator voltage drop from 1 2 to 5V Fig 16 Loop powered backlight Providing the increased voltage...

Page 25: ...l pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel b...

Reviews: