Technical data
Beijer Electronics AB, MA00557F
A-7
Technical data for CIMREX 20
Parameter
CIMREX 20
CIMREX 20 of hardware version
type no 04760 or higher
Front panel, W x H x D
147 x 163.5 x 5 mm
Mounting depth
38 mm excl. D-sub 107 mm
incl. D-sub
41 mm excl. D-sub 107 mm incl.
D-sub
Front panel seal
IP 65, NEMA 4X (indoor use only)
Rear panel seal
IP 20
Keyboard material
Membrane switch keyboard with polyester domes.
Overlay film of Autotex F207 * with print on reverse side.
1 million operations.
Reverse side material
Alu-Zinc
Weight excl. D-sub
0.7 kg
Serial port RS485
-
Available through RS422. Requi-
res software configuration
Serial port RS422
25-pin D-sub contact, chassis-mounted female with standard
locking screws 4-40 UNC.
Serial port RS232C
9-pin D-sub contact, chassis-mounted male with standard lock-
ing screws 4-40 UNC.
Flash memory for
application
64 kb
Real time clock
±10 PPM + error because of ambient temperature and supply
voltage. Total max error 1 min/month = 12 min/year.
Minimum life of real time clock battery: 10 years.
Power consumption at
rated voltage
Max: 150 mA
Display
STN-LCD. 4 lines of 20 characters, 5 mm character height.
LED backlight lifetime at the ambient temperature of +25
°
C:
50,000 h.
Active area of display,
W x H
70.4 x 20.8 mm
Contrast setting
Adjust potentiometer on the back of the terminal using an
appropriate tool, such as a plastic screw driver, in order to limit
the risk of short-circuiting or other injury.
Power supply
+24 V DC (20-30 V DC) 3-pin jack connection block.
CE: The power supply must conform with the requirements for
SELV or PELV according to IEC 950 or IEC 742. UL: The power
supply must conform with the requirements for class II power
supplies.
Summary of Contents for CIMREX 10
Page 1: ...CIMREX operator terminals Installation manual MA00557F 2004 04 Multi language...
Page 29: ...Beijer Electronics AB MA00557F 7 1 4 89 336 EEC EMC...
Page 94: ...Terminal drawings C 2 Beijer Electronics AB MA00557F CIMREX series Installation 24 V DC...
Page 95: ...Terminal drawings Beijer Electronics AB MA00557F C 3 CIMREX series Installation 115 230 V AC...
Page 97: ...Terminal drawings Beijer Electronics AB MA00557F C 5 232 25 ADP adapter to CIMREX 5...
Page 98: ...Terminal drawings C 6 Beijer Electronics AB MA00557F RS485 connection...
Page 100: ...Terminal drawings C 8 Beijer Electronics AB MA00557F CIMREX 5 Outline...
Page 101: ...Terminal drawings Beijer Electronics AB MA00557F C 9 CIMREX 10 Outline...
Page 102: ...Terminal drawings C 10 Beijer Electronics AB MA00557F CIMREX 12 Outline...
Page 103: ...Terminal drawings Beijer Electronics AB MA00557F C 11 CIMREX 20 Outline...
Page 104: ...Terminal drawings C 12 Beijer Electronics AB MA00557F CIMREX 30 Outline...
Page 105: ...Terminal drawings Beijer Electronics AB MA00557F C 13 CIMREX 41 Outline...
Page 106: ...Terminal drawings C 14 Beijer Electronics AB MA00557F CIMREX 60 Outline...
Page 107: ...Terminal drawings Beijer Electronics AB MA00557F C 15 CIMREX 67 CIMREX 69 CIMREX 69T Outline...
Page 108: ...Terminal drawings C 16 Beijer Electronics AB MA00557F CIMREX 70 Outline...
Page 109: ...Terminal drawings Beijer Electronics AB MA00557F C 17 CIMREX 90 Outline...
Page 110: ...Terminal drawings C 18 Beijer Electronics AB MA00557F CIMREX 90D Outline...
Page 111: ...Terminal drawings Beijer Electronics AB MA00557F C 19 CIMREX 91 Outline...
Page 112: ...Terminal drawings C 20 Beijer Electronics AB MA00557F CIMREX 91D Outline...