Beijer Electronics Frequency Inverter BFI-E3
KI00369C 2021-09
www.beijer.se www.beijer.no
www.beijerelectronics.de www.beijerelectronics.com www.beijerelektronik.com.tr
19 (28)
5.16 Control of BFI by Modbus TCP
BFI-E3 should have firmware version 3.11 (from August 2021) for full functionality. Default IP-
address of BFI-E3 is 192.168.1.253 and Subnet: 255.255.255.0. Enter the IP-address in a web browser
to access the web server inside BFI-E3. Username is Admin and Password is the serial number of the
BFI.
The double ethernet ports with same IP-address are called P1 and P2 as in the picture. The red
marked D1 and D2 are serial ports and must NOT be connected to an ethernet network
Communication working Communication interruption
Network Status Indicator, NS
State
Indication
Steady Off
BFI is not powered up or no IP address
Flashing Green
Online, no Modbus TCP connections active
Steady Green
Online, Modbus TCP connections active
Flashing Red
Connection Timeout after working Modbus TCP connection
Steady Red
Duplicate IP address
Para-
meter
Name
Default
settng
Recommended
setting
Function
P-12
Command Source
0
7
7= Control by CANopen och ramptime in P-03 and P-04.
8= Control by CANopen och ramptime sent by CANopen.
P-14
Parameter Access
0
201
201 = Parameters above P-14 accessable.
P-24
Fast Deceleration time
0
Fast Deceleration ramptime from 0 to 50 Hz.
P-25
Analog Output Funct.
8
13: Analog output controlled via fieldbus
P-36
Communication
Setting
(Power off/on
when parameter has
been changed)
125 kbit/sec
- Stationnumber 0-63. First Drive should be stationnumber 1.
- Communication speed, 125-1000 kbit/sek.
- Communication timeout. 0 = No timeout [msec]. 30, 100, 1000
or 3000 milliseconds
t => BFI decelerate and gives alarm when loss of communication.
r => BFI coast to stop when loss of communication.
P-61
Ethernet Service
Option
0
0: Resricted access to webserver interface
1: Enable all services..
P-62
Ethernet Service
Timeout
0 min
0: Cyber security settings will not change
1-60 min. Ethernet access to BFI during period set in P-62. When
time run out P-61 turns zero.
P-63
Modbus Mode
Selection
0
0: Communication lost when no messages on the bus.
1: Communication lost when no message to this specific slave.
NOTE! DI1 (terminal 2) must always be closed to 24 VDC to start