Beijer Electronics Frequency Inverter BFI-E3
KI00369C 2021-09
www.beijer.se www.beijer.no
www.beijerelectronics.de www.beijerelectronics.com www.beijerelektronik.com.tr
10 (28)
The Start/stop switch can be used in combination with parameter P-64 and P-65 and terminal 2 and
terminal 3 according to table below.
Explanation of the table:
-
P-64=0: Function DI1 active if terminal=24V or switch in right- or left position.
-
P-64=1: Function DI1 active if terminal=24V. Switches doesn’t effect DI1.
Parameter P-64
Input and Conditions
Function DI1
Terminal 2
0
24 V
OR
Run Fwd
OR
Run Rev
Active
1
24 V
*
*
Active
2
24 V
OR
Run Fwd
*
Active
3
24 V
AND
Run Fwd
OR
Run Rev
Active
4
24 V
AND
Run Fwd
*
Active
Parameter P-65
Terminal 3
Function DI2
0
24 V
*
OR
Run Rev
Active
1
24 V
*
*
Active
2
24 V
*
AND
Run Rev
Active
*= Means No function
By combining settings of P-12, P-15, P-64 and P-65 together with the switches and input signals on
terminal 2 and 3 it is possible achieve a number of very useful functions like “Start only if a sensor is
active”.
Layout Integrated Control Switch and Potentiometer wiring