Commissioning
EL34xx
221
Version: 1.5
Index F603 PMX Total Active
Index (hex) Name
Meaning
Data type
Flags
Default
F603:0
PMX Total Active
Max. subindex
UINT8
RO
0x14 (20
dec
)
F603:11
Active Power
Active power in W
INT64
RO
F603:12
Active Energy
Recorded active energy in mWh
INT64
RO
F603:13
Active Positive Energy Received active energy in mWh
INT64
RO
F603:14
Active Negative En-
ergy
Supplied active energy in mWh
INT64
RO
Index F604 PMX Total Active Fundamental
Index (hex) Name
Meaning
Data type
Flags
Default
F604:0
PMX Total Active
Fundamental
Max. subindex
UINT8
RO
0x14 (20
dec
)
F604:11
Active Power Fund
Active power of the fundamental oscillation in W
INT64
RO
F604:12
Active Energy Fund
Balanced active energy fundamental oscillation in
mWh
INT64
RO
F604:13
Active Positive En-
ergy Fund
Related active energy of the fundamental oscillation
in mWh
INT64
RO
F604:14
Active Negative En-
ergy Fund
Active energy fed into the system of the fundamental
oscillation in mWh
INT64
RO
Index F605 PMX Total Apparent
Index (hex) Name
Meaning
Data type
Flags
Default
F605:0
PMX Total Apparent
Max. subindex
UINT8
RO
0x14 (20
dec
)
F605:11
Apparent Power
Balanced apparent power in VA
INT64
RO
F605:12
Apparent Energy
Recorded apparent energy in mWh
INT64
RO
F605:13
Apparent Positive En-
ergy
Received apparent energy in mWh
UINT64
RO
F605:14
Apparent Negative
Energy
Supplied apparent energy in mWh
UINT64
RO
Index F606 PMX Total Apparent Fundamental
Index (hex) Name
Meaning
Data type
Flags
Default
F606:0
PMX Total Apparent
Fundamental
Max. subindex
UINT8
RO
0x14 (20
dec
)
F606:11
Apparent Power Fund Apparent power fundamental in VA
INT64
RO
F606:12
Apparent Energy
Recorded apparent energy in mWh
INT64
RO
F606:13
Apparent Positive En-
ergy
Received apparent energy in mWh
UINT64
RO
F606:14
Apparent Negative
Energy
Supplied apparent energy in mWh
UINT64
RO
Index F607 PMX Total Reactive
Index (hex) Name
Meaning
Data type
Flags
Default
F607:0
PMX Total Reactive
Max. subindex
UINT8
RO
0x14 (20
dec
)
F607:11
Reactive Power
Balanced reactive power in Var
INT64
RO
F607:12
Reactive Energy
Recorded reactive energy in mWh
INT64
RO
F607:13
Reactive Positive En-
ergy
Received reactive energy in mWh
UINT64
RO
F607:14
Reactive Negative
Energy
Supplied reactive energy in mWh
UINT64
RO
Summary of Contents for EL34 Series
Page 2: ......
Page 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Page 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Page 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Page 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Page 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Page 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Page 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Page 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Page 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Page 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Page 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Page 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...