Commissioning
EL34xx
182
Version: 1.5
Index 80n2 PMX User Scale (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
Meaning
Data type
Flags
Default
80n2:0
PMX User Scale Ch.1 Max. subindex
UINT8
RO
0x15 (21
dec
)
80n2:01
User Calibration En-
able
Set to true to enable user calibration data.
BOOLEAN
RW
0x00 (0
dec
)
80n2:11
User Calibration Volt-
age Offset
Value in V
REAL32
RW
0x00000000 (0
dec
)
80n2:12
User Calibration Volt-
age Gain
Factor (without unit)
REAL32
RW
0x3F800000
(1065353216
dec
)
80n2:13
User Calibration Cur-
rent Offset
Value in A
REAL32
RW
0x00000000 (0
dec
)
80n2:14
User Calibration Cur-
rent Gain
Factor (without unit)
REAL32
RW
0x3F800000
(1065353216
dec
)
80n2:15
User Calibration
Phase Offset
Value in milliseconds
REAL32
RW
0x00000000 (0
dec
)
Index F800 PMX Settings
Index (hex) Name
Meaning
Data type
Flags
Default
F800:0
PMX Settings
Max. subindex
UINT8
RO
0x16 (22
dec
)
F800:01
Reset Interval
Manual restart of the measurement and statistics in-
terval
BOOLEAN
RW
0x00 (0
dec
)
F800:11
Reference
Timing reference for the RMS calculation
Set to "Current" if a current is to be measured without
an applied voltage.
permitted values:
UINT32
RW
0x00000000 (0
dec
)
0
Voltage (default)
1
Current
F800:12
Measurement Range
Filter setting for determining the fundamental
permitted values:
UINT32
RW
0x00000000 (0
dec
)
0
25..65 Hz (default)
1
25..400 Hz
2
12..45 Hz
F800:13
Frequency Source
Source of the system frequency
permitted values:
BIT1
RW
0x00000000 (0
dec
)
0
Channel 1 (default)
1
Channel 2
2
Channel 3
F800:14
Power Calculation
Threshold
Noise reduction:
Here you can enter a minimum limit value in percent
for the power calculation, below which all values are
zeroed.
REAL32
RW
0x3F800000
(1065353216
dec
)
F800:15
Inaccurate Threshold
Voltage
Limit value for the warning bit: Inaccurate Voltage
REAL32
RW
0x3FDC28F6
(1071393014
dec
)
F800:16
Inaccurate Threshold
Current
Limit value for the warning bit: Inaccurate Current
REAL32
RW
0x3BC49BA6
(1002740646
dec
)
Index F801 PMX Total Settings PQF
Index (hex) Name
Meaning
Data type
Flags
Default
F801:0
PMX Total Settings
PQF
Max. subindex
UINT8
RO
0x13 (19
dec
)
F801:11
Nominal voltage
A nominal voltage value or set value is required to
calculate the power quality factor (for details see ba-
sic function principles).
REAL32
RW
0x43660000
(1130758144
dec
)
F801:12
Nominal Frequency
A nominal frequency or set value is required to calcu-
late the power quality factor (for details see basic
function principles).
REAL32
RW
0x42480000
(1112014848
dec
)
F801:13
PQF Dataset
permitted values:
UINT32
RW
0x00000001 (0
dec
)
0: default
1: d unbalace
Summary of Contents for EL34 Series
Page 2: ......
Page 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Page 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Page 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Page 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Page 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Page 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Page 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Page 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Page 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Page 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Page 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Page 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...