Product overview
EL34xx
21
Version: 1.5
EL3453
Technical data
EL3453
Number of inputs
4 x current, 3 x voltage
Technology
3-phase power measurement
Oversampling-factor
–
Distributed-Clocks
Optional (for zero crossing time determination)
Accuracy of Distributed Clocks
<< 1 µs
Update time
with every half-wave (10 ms at 50 Hz)
Measured values
Current, voltage, active power, reactive power, apparent power, active energy, reactive en-
ergy, apparent energy, fundamental wave power and energy, cos φ, frequency, THD, har-
monics (up to 63rd harmonic), power quality factor
Measuring error
0.3 % relative to full scale value (U/I)
0.6 % calculated values (see documentation)
Mains voltage
(Nominal voltage range)
corresponding to AC:
400 V
rms
(UL
X
-N) or 690 V
rms
(UL
X
-UL
Y
) (TN-system: 600 V
rms
)
Technical measuring range Voltage
520 V
rms
(UL
X
-N) or 897 V
rms
(UL
X
-UL
Y
)
common reference potential N/GND
max. time for voltages above 500 V
rms
(UL
X
-N)
or 863 V
rms
(UL
x
-UL
y
): t
max
< 10s *
Maximum permissible overvoltage
max. ±736 V (peak value, UL
X
-N, corresponds to 520 V
rms)
or
max. ±1270 V (peak value, UL
X
-UL
Y
, corresponds to 897 V
rms
)*
Internal resolution
24 bits
Input resistance Voltage path
typ. 1,5 MΩ
Nominal current range
corresponding to AC:
100 mA
rms
;1 A
rms
(default); 5 A
rms
recommended via measuring transformer x A AC/1 A AC
Technical measuring range current
2.25 A (peak value, corresponds to 1.59 A
rms
) or.
9.6 A (peak value, corresponds to 6.8 A
rms
)
Maximum permissible overcurrent
max. ±10 A peak value, corresponds to 7 A
rms
* per channel and
max. total current (I1+I2+I3+IN) ±20 A peak value, corresponds to 14 A
rms
*
Peak overload capacity
60 A (sinusoidal) for 1 second, upstream use of current-limiting current transformers recom-
mended
Largest short-term deviation during a
specified electrical disturbance test
< ±0.5% of full scale value for current measurement
Input resistance Current path
typ. 3 mΩ
Frequency range
15 … 400 Hz
Threshold frequency
4000 Hz
Electrical isolation
4500 V
Current consumption power contacts
–
Current consumption E-Bus
260 mA typ.
Weight
approx. 100 g
Dimensions (W x H x D)
approx. 27 mm x 100 mm x 70 mm (width aligned: 24 mm)
Mounting
on 35 mm mounting rail according to EN 60715
Permissible ambient temperature range
during operation
0°C ... +55°C
Permissible ambient temperature range
during storage
-25°C ... +85°C
Relative humidity
95 % no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2/EN 61000-6-4
Protect. class / installation pos.
IP20/any
Approvals
CE
*) prolonged operation above the nominal range can lead to impairment of function and/or shortening of operating life
Summary of Contents for EL34 Series
Page 2: ......
Page 52: ...Mounting and wiring EL34xx 52 Version 1 5 Fig 35 Other installation positions ...
Page 58: ...Mounting and wiring EL34xx 58 Version 1 5 EL3453 LEDs and connection Fig 40 EL3453 LED s ...
Page 92: ...Commissioning EL34xx 92 Version 1 5 Fig 86 Incorrect driver settings for the Ethernet port ...
Page 130: ...Commissioning EL34xx 130 Version 1 5 Fig 147 Process Data tab SM3 EL3443 ...
Page 131: ...Commissioning EL34xx 131 Version 1 5 Fig 148 Process Data tab SM3 EL3453 ...
Page 132: ...Commissioning EL34xx 132 Version 1 5 Fig 149 Process Data tab SM3 EL3483 ...
Page 160: ...Commissioning EL34xx 160 Version 1 5 Index F802 PMX Guard Settings ...
Page 183: ...Commissioning EL34xx 183 Version 1 5 Index F802 PMX Guard Settings ...
Page 205: ...Commissioning EL34xx 205 Version 1 5 Index 1C13 TxPDO assign ...
Page 214: ...Commissioning EL34xx 214 Version 1 5 Index F802 PMX Guard Settings ...
Page 242: ...Commissioning EL34xx 242 Version 1 5 Index 1C13 TxPDO assign ...
Page 259: ...Application examples EL34xx 259 Version 1 5 7 Application examples ...