Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 41 of 260
Version: 25F
Technical characteristic data
SMX131(/2), 131R(/2) und 131R-4/2
Safety related characteristic data
Pl acc. to EN ISO 13849-1
PL e
PFH / architecture
9,2 FIT
/Cat 4
1)
plus in SMX31R/31R-4
1-channel per Rel 20 FIT
(
max. 8)
2-channel per Rel 1,0 FIT
(
max. 4)
SIL acc. to IEC 61508
SIL 3
Proof test interval
20 years = max. operating period
General data
Max. no. of expansion modules
-
Interface for expansion modules
T-bus connector, pluggable in top-hat rail
Number of safe digital inputs
12 (OSSD capable)
Number of safe digital outputs
-
Number of safe digital I/O
SMX131(/2)
10
SMX131R(/2)
2
SMX131R-4/2
6
Number of relay outputs
SMX131R(/2)
8
SMX131R-4/2
4
Number of safe analogue inputs
-
Number of auxiliary outputs
2
Number of pulse outputs
(clock outputs)
2
Type of connection
Plug-in terminals with spring or screw connection
Axis monitoring
-
Encoder interfaces
(D-Sub / screw terminal)
-
Encoder technology
(See table encoder specifications)
-
SMXGen2 (/2)
Number of safe digital outputs
pn-switching **
2
pp-switching **
4
Electrical data
Fuse
X11.1
min. 30 VDC; max. 3,15A
Max. power consumption
(logic)
2,4W
Rated data digital inputs
24 VDC; 20 mA, Typ1 acc. to EN 61131-2
Rated data digital outputs
Auxilary outputs
24 VDC; 250mA
Pulse outputs
(clock outputs)
24 VDC; 250mA
Digital I/O
24 VDC; 250mA
Rated data
relays
Normally open
DC13
AC15
24 VDC; 2A
230 VAC; 2A
Normally closed
DC13
(Read back contact)
24 VDC; 2A
Rated data analogue inputs
-
SMXGen2 (/2)
Fuse
X11.1
min. 30 VDC; max. 10A
Max. power consumption
(logic)
3W
Rated data digital outputs
Digital I/O
01
– 05
06
– 10
24 VDC; 0,5A
24 VDC; 2A ***
Electrical data (For UL only) SMXGen2 (/2)
Rated data digital outputs
Auxilary outputs
24 VDC; 250mA (G.P.)
Digital I/O
01
– 05
24 VDC; 0,5A (G.P.)
06
– 10
Temperature rating
30°C
24 VDC; 2A (G.P.)
Temperature rating
50°C
24 VDC; 1,8A (G.P.)
Max. total current I/O
10A
Rated data
relays
Normally open
24 VDC; 2A (Pilot Duty
)
120 VAC; 2A (Pilot Duty
)
Normally closed
(Read back contact)
24 VDC; 2A (Pilot Duty
)
Environmental data
Temperature
0°C … +50°C operation