Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 214 of 260
Version: 25F
With overspeed distance the following connections result for the course of V and s.
Parameters
Calculation methods
Comment
t
Response
Value for response time data SMX +
deceleration time in external shut-down
chain
Deceleration time in external shut-off
chain derived from relay/contactor
and brake data, etc. issued by the
manufacturer
a
F
, a
V
n.a.
Estimation of the application
V
a2
= a
F
* t
Response
+ (V
S
2
+ 2 * a
F
* XF)
1/2
With its effect the filter displaces the set speed threshold V
a
upwards by the amount
delta_v_filter
. For the application one must consider the new response time values
(Treact = Tsmx + Tfilter), as well as the speed at shut-down by SMX100 resulting from this.
6.4 Reaction times for using inputs and outputs at the expansion
modules
The cycle time of the SMX system serves as basis for calculating the response times. In
operation this is
T_
Cycle = 16 / 24 / 32 ms
. The specified response times comply with the
corresponding maximum running time for the actual application within the SMX100 module.
Depending on the application, further, application dependent response times of the sensors and
actuators used must be added, in order to obtain the total running time.
Function
Designatio
n
Response
time [ms]
Explanation
Worst Case deceleration time inlet
in basic module to PAE
T
IN_BASE
T
Cycle
e.g. activation of a monitoring function
by an input signal in the basic module
Worst Case deceleration time input
expansion module to PAE in base
module
T
IN_Erw
T
Cycle
+ 6ms
e.g. activation of a monitoring function by an
input signal in the extension module
SMX31
Processing time PAE to PAA in
basic module
T
PLC
T
Cycle
Shut-down by a monitoring function or an
input in PAE
Activation / deactivation digital
output in basic module from PAA
T
OUT_BASE
-
Activation or deactivation of an output in
the basic module after changes to the
PAA.
Activation / deactivation digital
output in extension module via
PAA in basic module
T
OUT_Erw
T
Zyklus
+ 8ms
Activation or deactivation of an output in
the extension module SMX31 after
changes to the PAA in the basic module.