Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 107 of 260
Version: 25F
o
at a load resistance < 100 Ω with a holding capacity > 0.4 mW
Only relevant with SMXGen2 (/2) to HW release 11-xx-
xx…
•
For the output system a vast number of diagnostic measures have been implemented.
Special attention must be paid to the inclusion of elements for switching amplification,
such as relays, contactors, etc. in the cutout circuit.
4.3.4.2 Wiring examples basic outputs
4.3.4.2.1 Single-channel switching relay or semi-conductor output without test
For the connection of multi-phase applications or for higher current demands external contactors
may be used. For a single-pole connection without external test please bear in mind that the
SMX100 module will not recognize bonding of one or several external contacts. The following
circuit example is only limited suitable for safety applications, Pl b acc. to EN ISO 13849-1 can
maximally be achieved!
Q1_PP
X21
X14
Q2_PN
Q3_PP
Q4_PN
I01
I02
I03
I04
L+
L-
Fig.: Single-channel switching P-output.
Q5.1
Q5.2
Q6.1
Q6.2
L+
L-
X22
Fig.: Single-channel switching relay output.
Safety note:
•
Not recommended for safety applications! In this context see also the notes in EN ISO
13849-1 concerning the application and the required fault exclusions.