Installation manual
HB-37420-810-01-25F-EN SMX100 Installation manual.docx
Page 218 of 260
Version: 25F
Bus status
b0003
Message
Communication structure with slave module
Cause
Slave units is not registering
Troubleshooting
Check address slave unit.
Check status LED slave module (must be blinking green)
Check mechanical structure SMX100
Bus status
b0012
Message
Bus error
Cause
Bus error due to defective slave units
Troubleshooting
Configured slave module (e.g. SMX122) does not match the existing
slave module (e.g. SMX122A)
Check status LED slave module (must be blinking green)
7.3 LED display
Colour
Mode
Description
green
"flashing"
System OK, configuration
validated
yellow
"flashing"
System OK, configuration
not yet validated
red
"flashing"
Alarm
red
"permanent"
Fatal Fault
yellow - red
"flashing"
System OK, configuration
not yet validated, SMMC
configured however participant is
missing
green - red
"flashing"
System OK, configuration
validated, SMMC configured
however participant is missing
Note:
For all operating states except RUN the outputs are rendered passive by the firmware, i.e.
safely switched off. In status RUN the state of the outputs depend on the implemented PLC-
program.