MX08 Multichannel Weighing System, Technical Manual, Rev. 2.5 Page 59 of 144
Set all outputs of MX08 IO [0] at register 41071.
Request
: 01, 10, 04, 2E, 00, 01, 02, 00, 0F, A5, DA
Answer
: 01, 10, 04, 2E, 00, 01, 60, F0
Outputs activated.
Zeroing MX08 AD [0] at register 41062.
Request
: 01, 10, 04, 25, 00, 01, 02, 00, 01, 25, 65
Answer
: 01, 10, 04, 25, 00, 01, 11, 32
MX08 AD [0] is zeroed.
Zeroing MX08 AD [1] at register 41063.
Request
: 01, 10, 04, 26, 00, 01, 02, 00, 01, 25, 56
Answer
: 01, 10, 04, 26, 00, 01, E1, 32
MX08 AD [1] is zeroed.
Taring MX08 AD [0] at register 41062.
Request
: 01, 10, 04, 25, 00, 01, 02, 00, 02, 65, 64
Answer
: 01, 10, 04, 25, 00, 01, 11, 32
MX08 AD [0] is tared.
Taring MX08 AD [1] at register 41063.
Request
: 01, 10, 04, 26, 00, 01, 02, 00, 02, 65, 57
Answer
: 01, 10, 04, 26, 00, 01, E1, 32
MX08 AD [1] is tared.
Zero Calibration of MX08 AD [0].
Request
: 01, 03, 04, 66, 00, 01, 65, 25 (Read status; it must be in ready status)
Answer
: 01, 03, 02, 00, 01, 79, 84 (MX08 AD [0] is in ready status; zero calibration
can be performed)
Request
: 01, 10, 04, 63, 00, 01, 02, 00, BC, EB, B2 (Zero calibration command)
Answer
: 01, 10, 00, 6D, 00, 01, 90, 14
Request
: 01, 03, 04, 66, 00, 01, 65, 25 (Read status; it must be in ready status)
Answer
: 01, 03, 02, 00, 01, 79, 84 (If it changed “zeroing” to “ready” status, zero
calibration is performed successfully.)
Span Calibration of MX08 AD [0].
Request
: 01, 03, 04, 66, 00, 01, 65, 25 (Read status; it must be in ready status)
Answer
: 01, 03, 02, 00, 01, 79, 84 (MX08 AD [0] is in ready status; span calibration
can be performed)
Request
: 01, 10, 04, 63, 00, 03, 06, 00, DC, 00, 00, 0B, B8, D6, 90
(Span calibration command with 3000 (0x0BB8 hex) span value)
Answer
: 01, 10, 00, 6D, 00, 03, 11, D5
Request
: 01, 03, 04, 66, 00, 01, 65, 25 (Read status; it must be in ready status)
Answer
: 01, 03, 02, 00, 01, 79, 84 (If it changed “span calb” to “ready” status, span
calibration is performed successfully.)
Exception codes:
1: Function code is not supported
2 : Received data address is not in allowable address range
3 : Invalid value entrance or wrong byte number
4 : Operation error