MX08 Multichannel Weighing System, Technical Manual, Rev. 2.5 Page 31 of 144
I
Read indicated weight
Command :
[ADR][I]
Response :
[ADR][I][STATUS][SIGN][WEIGHT VALUE]
Example
:
Command
: 12I
Response
: 12IS+000123.4
( weight is stable and 123.4 )
12ID+000123.4
( weight is dynamic and 123.4 )
12I+
( overload )
Comments :
The response is the indicated weight value (stable or dynamic). It will be transmitted
immediately after receiving the command.
The weight value may be in gross or net.
P
Print : Read the stable weight
Command :
[ADR][P]
Response :
[ADR][P][STATUS][SIGN][WEIGHT VALUE]
Example
:
Command
: 12P
Response
: 12PS+000123.4 (weight is stable and 123.4) or
12PN
(could not print)
Comments :
Checks status and it must be stable. Else Nack status is send.
There is no time duration for stability checking.
Status can be Stable or Nack.
S
Read Status
Command :
[ADR][S]
Response :
[ADR][S][STATUS-1][STATUS-2][STATUS-3]
Example
:
Command
: 12S
Response
: 12SSGI
(Stable, Gross, In Range)
: 12SDGL
(Dynamic, Gross, Low voltage error)
Comments :
The response is current 3 status information.
STATUS-1 can be Stable or Dynamic.
STATUS-2 can be Gross or Net.
STATUS-3 can be ‘in range’, ‘out of range’, ‘low voltage’ or ‘high voltage’.
T
Tare
Command :
[ADR][T]
Response :
[ADR][T][A] (Taring is done successfully and scale is in net)
[ADR][T][N] (Taring could not executed)
[ADR][T][X] (Taring is disabled or instrument is in count mode)
Comments :
The tare value is overwritten by the new tare weight value.
Status must be stable in 2 seconds time out delay. If so, Ack is send.
If it can not be stable in time out delay, Nack is send.