MX08 Multichannel Weighing System, Technical Manual, Rev. 2.5 Page 125 of 144
13.5. EtherCAT Data Structure
Please refer to the Section 3.5 for detailed PLC configuration.
MX08 EC Output to PLC Input
Bitwise of Dword:
Dword
(R/W)
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
D15 D14 D13 D12 D11 D10 D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
G
at
ew
ay
1st
Dword
(R)
Active MX08 IO instruments
Active MX08 AD instruments
Error Table
Not in use
Cmd
Flg
Bit
Number
1
st
Dword Description
D31
0: No instrument found 1: 7 addressed MX08 IO is active
Active IO
instruments
D30
0: No instrument found 1: 6 addressed MX08 IO is active
D29
0: No instrument found 1: 5 addressed MX08 IO is active
D28
0: No instrument found 1: 4 addressed MX08 IO is active
D27
0: No instrument found 1: 3 addressed MX08 IO is active
D26
0: No instrument found 1: 2 addressed MX08 IO is active
D25
0: No instrument found 1: 1 addressed MX08 IO is active
D24
0: No instrument found 1: 0 addressed MX08 IO is active
D23
0: No instrument found 1: 7 addressed MX08 AD is active
Active AD
instruments
D22
0: No instrument found 1: 6 addressed MX08 AD is active
D21
0: No instrument found 1: 5 addressed MX08 AD is active
D20
0: No instrument found 1: 4 addressed MX08 AD is active
D19
0: No instrument found 1: 3 addressed MX08 AD is active
D18
0: No instrument found 1: 2 addressed MX08 AD is active
D17
0: No instrument found 1: 1 addressed MX08 AD is active
D16
0: No instrument found 1: 0 addressed MX08 AD is active
D15
D14
D13
D12
0000
No error found
Error Codes
of MX08 EC
0001
System fails.
− Re-energize the instrument. If seen again, change the board.
0010
EEPROM fail.
− Re-energize the instrument. If seen again, change the board.
0011
Field bus module error.
− Re-energize the instrument.
− Check the field-bus module is installed on the board.
− If seen again, change the board.
0100
No Instrument found on N-Bus.
− Install Digitizer or I/O instruments to the system.
− Check N-BUS connectors whether they are installed.
0101
An instrument is installed/removed in/from system.
− Re-address the instruments on N-Bus (Refer to section 3.3 or
Section 3.9 N-Bus addressing)
D11…D1 Not in use
D0
Toggles
The command is applied successfully
CMD Flag