Parameter number
Parameter
Description
Unit
Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
760
1060
1360
R
Room temp
limitation
Cuts the heating circulation pump if the room T
° exceeds the current set point + parameter
760, 1060, 1360
°C
00.5
809
1109
1409
C
Continuous pump
operation
No : The heating circuit / boiler pump may be
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de
cline in temperature and when the room tem
perature set point is reached.
–
no
834
1134
1434
A
Actuator running
time
Setting the stroke of the servomotor on the
mixing valve used
seconds 30
850
1150
1450
FFloor curing
function
Controlled screed-drying function:
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at a T° of 25°C and 4 days at a T° of
55°C
Curing heating : Active for 18 days, 6 days
from 25°C to 55°C increasing by 5°C a day,
6 days at a T° of 55°C, 6 days from 55°C to
25°C diminishing by 5°C a day.
Functional/curing heating : First, "Functional
Heating" cycle, and then, "Ready for Occu
pation".
Functional heating : First, "Ready for Occu
pation" cycle, and then, "Functional Heating".
Manually : Regulation is based on the "Man
ual Control Drying" set point.
S
O
Off
851
1151
1451
FFloor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C
25
855
1155
1455
FFloor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘ ---‘ the function is
deactivated.
-
‘---’
856
1156
1456
D
Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘ ---‘ the function is deactivated.
-
‘---’
Tab.46 Menu TTemps / mode hot water
Parameter
number
Parameter
Description
Factory setting
1600
O
Operating mode
Off Permanent running on the antifreeze set point
On DHW loading is done automatically at the nominal set point
EcoThe temperature maintenance function is deactivated
On
1610
H
Hot water temp
setpoint
DHW set point during release times
660°C
1612
R
Reduced temp
setpoint
Reduced set point outside release times
335°C
1620
R
Release
Start-up enabled:
Time hot water : This setting provides DHW preparation with a
dedicated timer program.
Time setting central heating : The release of DHW is done in //
of the period of occupation of the heating circuits.
24h/day : Default setting for instantaneous boilers.
Time hot water
9 Settings
76