Tab.44 Menu W
Wireless
Parameter
number
Parameter
Description
120
B
Binding
Activation of wireless connection with the base unit.
121
TTest mode
The test mode is used to check the wireless communication.
130
R
Room unit 1
Checking the link.
131
R
Room unit 2
Checking the link.
132
R
Room unit 3
Checking the link.
133
O
Outside temperature
sensor
Checking the link.
134
R
Repeater
Checking the link.
135
IIn operation
Checking the link.
140
D
Delete all devices
Deletes all appliances
Tab.45 Menus TTemps / mode CH1 – TTemps / mode CH2 – TTemps / mode CH3
Parameter number
Parameter
Description
Unit
Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
714
1014
1314
FFrost protection
setpoint
°C
6
720
1020
1320
H
Heating curve
slope
Heating curve gradient: The regulator calcu
lates the flow T° set point which is used for the
control system, according to outside weather
conditions.
–
Heating
circuit 1:
1.5
Heating
circuit 2:
0.7
Heating
circuit 3:
0.7
730
1030
1330
S
Summer/winter
heating limit
Limit temperature for Heating/Frost Protection
Mode switching. Triggers or shuts down the
heating in the course of the year according to
variations in outside T°. This switch is made
automatically in Automatic mode.
20
732
1032
1332
224-hour heating
limit
The heating is shut down when the outside T°
is equal to the room tempe parameter
732 (deactivated in Comfort mode).
°C
0
740
1040
1340
FFlow temp
setpoint min
The flow set point calculated is limited by the
set value.
°C
25
741
1041
1341
FFlow temp
setpoint max
The flow set point calculated is limited by the
set value.
°C
80
742
1042
1342
FFlow temp
setpoint room stat
The set flow value is applied in room tempera
ture thermostat mode. ‘ ---‘ the boiler is running
in modulation mode.
°C
80
746
1046
1346
D
Delay heat
request
750
1050
1350
R
Room influence
Influence of the room T° and the outside T°
on calculating the flow temperature: ---%:
Simple regulation in accordance with outside
weather conditions
1…99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
%
50
9 Settings
7609474 - v02 - 04092014