Tab.42 Menu TTemps / mode CH1 – Temps / mode CH2 – Temps / mode CH3
Parameter number
Parameter
Description
Factory setting
Heating
circuit 1
Heating
circuit 2
Heating cir
cuit 3
700
1000
1300
Operating
mode
The control unit is installed on the boiler:
Off: heating is deactivated.
Timed: heating is dependent on the hourly pro
gram.
Reduced: heating is in permanent reduced mode.
On: heating is in permanent comfort mode.
The control unit is installed as a room temperature
control system:
Off: the boiler starts up when the room tempera
ture falls below the frost protection set point.
Timed: heating is dependent on the hourly pro
gram.
Reduced: the room temperature set point is the
reduced set point (parameters 712, 1010, 1310)
On: the room temperature set point is the comfort
set point (parameters 710, 1010, 1310)
On
710
1010
1310
Comfort
setpoint
20°C
712
1012
1310
Reduced
temp setpoint
16°C
9.1.4 List of installer parameters
Tab.43 Menu O
Operator section
Parameter
number
Parameter
Description
Factory set
ting
24
LLighting
Off
Temporarily
Permanently
Temporarily
29
U
Units
°C, bar
°F, PSI
°C, bar
40
U
Used as
Operator unit 1 : The control system unit is installed on the boiler.
Room unit 1 : The control system unit is configured as a room tem
perature appliance for heating circuit 1.
Room unit 2 : The control system unit is configured as a room tem
perature appliance for heating circuit 2.
Room unit 3 : The control system unit is configured as a room tem
perature appliance for heating circuit 3.
Operator unit
1
42
A
Assignment device
1
Like Room Temperature Unit 1, the action of the control system unit
can be assigned to CC1 or to two heating circuits:
Temps / mode CH1
Central heating 1 and 2
Central Heating 1 and 3
All central heatings
All central
heatings
43
A
Action operation
Locally : The room temperature appliance only controls the respec
tive heating circuit.
Centrally : Only room temperature appliance 1 can be centralised. It
also controls the domestic hot water and standby mode.
Centrally
54
R
Readjustment room
sensor
-3°C to +3°C
0°C
70
S
Software version
9 Settings
74