66.5.5 Lengths of the air/flue gas pipes
Note
For configurations B
23
and C
93
, the lengths given in the tables are
valid for horizontal pipes with a maximum length of 1 metre. For
each additional metre of horizontal pipe, subtract 1.2 m from the
vertical length L
max
.
Tab.16 Maximum length
Configura
tion
Unit
POWER HT+ 1.50
POWER HT+ 1.70
POWER HT+ 1.90
POWER HT+ 1.110
mm
Ø 80
Ø 125
Ø 80
Ø 125
Ø 110
Ø 160
Ø 110
Ø 160
1
m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
2
m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
3
m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
4
m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
5
m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
6
m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
L<10 m
7
m
L<8 m
L<8 m
L<8 m
L<8 m
L<8 m
L<8 m
L<8 m
L<8 m
8
m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
L<9 m
9
m
L
1
+ L
2
<60 m
L
1
<15 m
–
L
1
+ L
2
<27
m
L
1
<15 m
L
2
<20 m
–
L
1
+ L
2
<27 m
L
1
<7 m
–
L
1
+ L
2
<27
m
L
1
<7 m
–
6 Installation