Due to the operating principle a leakage current
>
3,5 mA
AC
or
>
10 mA
DC
can flow via the protective conduc-
tor. On this account a permanent protective conductor is required.
At the
b maXX® BM3400
in addition to the plugged protective connection, the screw terminal, which is
marked with "PE" must be connected to the PE.
WARNING
The following
may occur
, if you disregard these safety notes:
• serious personal injury
• death
This device can lead to direct current in the protective conductor. If, in case of a direct or
indirect contact a residual-current-operated protective device (RCD) is used, then a RCD of
type B is permitted on the power supply side only. Otherwise other safety precautions, as e.g.
environmental separation with a double or strengthened insulation or by the separation of the
power supply with an isolated transformer must be used.
Due to high leakage currents, which arise due to the operating principle of the device can result in an early
enabling of the RCD or generally can avoid an enable.
b maXX® BM3400
devices may only operate in connection to public mains if mains filters are used.
If several
b maXX® BM3400
devices are operated in a switching cabinet, devices without internal mains
filter are recommended. In this case a common external mains filter must be used, which has to be selected
according to the sum of the currents of all devices used in the switching cabinet. Usually external mains filters
are filters of higher order and they produce less leakage current than internal mains filters.
60
Instrution
Manual
b
maXX®
BM3400
from
206
Do
ument
No.:
5.07013.03
Baumueller
Kamenz
GmbH
Summary of Contents for b maXX BM3400 Series
Page 1: ...E 5 07013 03 Instruction Manual b maXX BM3400 ...
Page 2: ......
Page 4: ......
Page 195: ...F Appendix F Index Instru tion Manual b maXX BM3400 195 Do ument No 5 07013 03 from 206 ...
Page 204: ......
Page 205: ... ...