Installation
Figure 6.4: Cabling power unit
• When installing, pay attention to the correct order of the components: Mains - Fuse - Mains filter -
Mains choke (depending on the converter) - Toroidal core (only at Mains filters
≥
250A) - Converter -
Motor.
• The compliance with the permissible limit values of the interference resistance and the interference
emission can only be assumed, if you exclusively use Baumüller motor cables and -components.
• The maximum length of motor cable is limited. The length of the motor cable is dependent on the cross
section of the cable (e.g. 100m at 1.5mm
2
, 30m at 35mm
2
). In case you use n parallel-installed motor
cables, the maximum length must be reduced to factor 1/n.
• The screened motor cable between converter and motor must be made of one piece. Do not interrupt
the cable e.g. by terminals, contactors, fuses and so on.
62