Troubleshooting and fault correction
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
87
9
9.2.1
Monitoring functions - explanations
Mains
voltage
Warning:
This monitoring function checks, if the mains voltage has a value within the adjusted volt-
age range. If the value is lower than the set value in P1354, the warning „mains under-
voltage“ is generated. If the value is higher than the set value in P1355, the warning
„mains overvoltage“ is generated.
Error:
If the value is lower than an intern set value, the error „mains undervoltage“ is generated.
If the value is higher than an intern set value, the error „mains overvoltage“ is generated.
In released status an immediate pulse inhibit result from an error message mains over-
voltage or mains undervoltage.
Phase
monitoring
This monitoring function checks the three phases of the mains voltage. If an outer con-
ductor is missing, the warning „Phase failure“ is reported.
If all three phases are missing, the warning „mains failure“ is indicated to the controller.
Mains frequency
monitoring
This monitoring function checks the following:
n
If the mains frequency value is within the permissible frequency range. If the value is
lower or higher the controller generates an error message „Frequency range error“ and
an immediate pulse inhibit occurs.
n
If the mains frequency change is too high. If the mains frequency change is > 5 Hz/s
the controller generates an error message „Frequency change error“ and immediately
a pulse inhibit occurs.
Controller synchronizing
Controller not synchronous with ext. signal X
X
X
X
3)
P0533 P0299
Module monitoring
2)
Wrong module
-
X
-
-
IS
-
-
Module is missing
-
X
-
-
IS
-
-
Wrong slot
-
X
-
-
IS
-
-
Ramp-up option modules
Error at module initialization
-
X
X
-
IS P0838 P0838
Cyclical set point transmis-
sion to the optional modules
Transmission timeout
-
X
X
X
4)
P0839 P0298
Monitoring current limit
Current limit reached
-
X
X
-
IS P1260 P1260
Monitoring signal
main contactor
no monitoring signal main contactor
-
X
X
-
IS P1356 P1356
Monitoring function
Warning/error
War
n
ing
Err
o
r
Th
res
hold adjus
tab
le
Re
ac
ti
on
ad
ju
s
ta
b
le
Reaction
Adjust
ing of
Limit in parameters
Act
ivat
ion by
Par
a
meters
1)
Pulse inhibit operates according to adjustable time
2)
Four function modules are necessary for the mains inverter
3)
Adjustable with P0299
4)
Adjustable with P0298
IS: Pulse inhibit