Technical Data
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
35
3
4)
At rated input voltage the device supplies the rated/maximum output currents. At input voltages above the rated input voltage the output
currents must be reduced accordingly at constant output power.
Figure 11:
Derating curves input current BM4163
5)
This overload time is dependent on the motor current and of the heatsink temperature and is determined by the Ixt-monitoring of the
device.
6)
The mains current is reduced by
at mains voltage of e.g. 480 V
AC
and permitted output power DC link (instead of 235 A
AC
the mains current is 195,8 A
AC
). When selecting the connected drives ensure that the output power of the DC link is not exceeded.
Figure 12:
Derating curve output power DC link BM4163
7)
This power output is only permitted for short periods of time (max. 60 s). This must be ensured by parametrization of the connected
drives.
8)
Incl. mains chokes
9)
Only valid for cooling variant S.
Input
cur
rent [%
]
Input voltage [V]
Peak current
Max. operation cur-
rent
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
350
400
450
500
Output
power D
C
link [%]
Input voltage [V]
400
480
----------
0 833
,
=
Summary of Contents for b maXX 4100 Series
Page 143: ......