Error handling
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
Baumüller Nürnberg GmbH
104
9.4
9.4.3
Warnings
P0261
Warning power supply
P0262
Warnings power unit
Warning No.
Meaning
Troubleshooting
0
not assigned = 0
1
Undervoltage 24 V
Assure the compliance with the specifications
2
Undervoltage power supply
Assure the compliance with the specifications
(see
Requirements to the energy supply / supply system
3
Overvoltage power supply
4
Power failure
Power supply troubleshooting
5
Phase failure
Check if all phases are correctly connected and voltage-carrying
6
Phase sequence identification
Check if all phases have correctly connected to the
BM4-F-UME-01 - module and are carrying voltage
7
Frequency change
Assure the compliance with the specifications
(see
Requirements to the energy supply / supply system
8
Frequency range
9
Mains connections
Check the connections of
BM4-F-UME-01 module and of the mains terminals
10
Pre-charge is running
Wait until the pre-charging has been completed, check if the
mains voltage is connected
11
Undervoltage U DC link
Check power connections
12
Synchronization
Check power connections
13
Exceeding the set power capacity
Reduce power
14 to 15
not assigned = 0
Warning No.
Meaning
Troubleshooting
16
Internal temperature of device
Establish the specified environmental conditions, assure correct
ventilation conditions
17
Heat sink temperature
Reduce the power output, check the fans of the device
18 to 23
reserved warning
24
Ixt threshold 1 exceeded
Reduce power drain
25 to 31
not assigned = 0