5-8
BE1-50/51B-230/-234 Testing
9252000894 Rev D
d. Set CURVE to V.
e. Set TIME PICKUP to 0.2.
f.
Set INST PICKUP (50-A) to 18.0.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (3.0 Aac).
2. Apply 0.8 Aac to terminals 5 and 6. After the unit trips, remove the applied current for 29
±
0.25
seconds, then reapply the current (0.8 Aac). Note the elapsed time from the reapplication of current to
the second trip. The elapsed time should be 2.08
±
0.4 seconds.
Figure 5-5. 51 Pickup, Time Dial, and Integrating Reset Test Setup
Instantaneous Overcurrent A (50-A) Pickup
1. Connect and configure the relay for 50-A pickup testing:
a. Connect the test setup shown in Figure 5-6.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (GE IAC type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 3.18.
f.
Set INST PICKUP (50-A) to 0.4.
g. Set INST PICKUP (50-B) (accessed at the top side of the assembly) to F0 (3.0 Aac).
2. Apply and slowly increase current to terminals 5 and 6 until the 50-A output contacts close. The
applied current should be between 0.387 and 0.413 Aac.
3. Decrease the applied current until the 50-A output contacts open.
4. Set INST PICKUP (50-A) to 1.6.
5. Slowly increase the current applied to terminals 5 and 6 until the 50-A output contacts close. The
applied current should be between 1.563 and 1.637 Aac.
6. Reduce the applied current to zero.
Summary of Contents for BE1-50B-230
Page 2: ......
Page 6: ...iv BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 8: ...vi BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 10: ...ii BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 18: ...1 8 BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 32: ...ii BE1 50 51B 230 234 Installation 9252000894 Rev D This page intentionally left blank...
Page 38: ...ii BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...
Page 50: ...5 12 BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...