9252000894 Rev D
BE1-50/51B-230/-234 General Information
1-5
BE1-50/51B-234 Burden
Figure 1-4 illustrates the current sensing input burden characteristic.
At 0.1 Aac:
57.0
Ω
At 1.0 Aac:
6.9
Ω
BE1-50/51B-234 CT Burden
0
20
40
60
80
100
120
140
0
2
4
6
8
10
Input Current (Amps)
B
u
rd
e
n
in
VA
(
rms
)
Figure 1-4. Current Sensing Input Burden (BE1-50/51B-234)
Frequency Response
A change of
±
5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for
pickup.
Transient Response
<10% overreach with system time constants up to 40 ms.
Harmonic Rejection
Rejection of odd and even harmonics is illustrated in Figure 1-5.