9252000894 Rev D
BE1-50/51B-230/-234 Testing
5-1
SECTION 5
•
TESTING
INTRODUCTION
Proper relay operation may be confirmed by performing the test procedures in this section.
DIELECTRIC TEST
In accordance with IEC 255-5 and IEEE C37.90-1989, one-minute dielectric (high potential) tests may be
performed as follows:
All circuits to ground:
2,828 Vdc or 2,000 Vac
Input to output circuits:
2,828 Vdc or 2,000 Vac
Output contacts are surge protected.
TEST PROCEDURES
The following test procedures verify operation of the BE1-50/51B-230 and BE1-50/51B-234 relays. The
test setups illustrated in Figures 5-1 through 5-8 are intended primarily as an illustration of the principles
involved. Other test equipment known to be capable of testing with the stated and implied tolerances
(including equipment designed specifically for testing protective relays) may be used.
The minimum test equipment requirements are:
•
Current source with a range of 0 to 20 Aac (sensing input current)
•
Current source with a range of 0 to 3.0 Aac (target operation)
•
Timer or counter
Model BE1-50/51B-230 (Five Ampere Sensing Input)
Time Overcurrent (51) Pickup
1. Connect and configure the relay for 51 pickup testing:
a. Connect the test setup shown in Figure 5-1.
b. Set circuit board switch SW3 as follows:
SW3-1 = ON for 50 Hz operation or OFF for 60 Hz operation
SW3-2 = OFF (no additional time delay for the 50-A element)
SW3-3 = ON (GE IAC type characteristic curves)
SW3-4 = ON (integrating reset characteristic)
c. Set the TIME DIAL to 0.0.
d. Set CURVE to S.
e. Set TIME PICKUP to 0.5.
NOTES
To ensure proper timing during testing, remove the current from the relay for R
times D seconds. (Refer to Appendix A,
Characteristic Curves
for definitions of R
and D.
When testing time overcurrent functions, instantaneous pickup settings of 00 will
affect the calibration of the time functions. Time pickup settings of 00 also affect
instantaneous functions.
When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect
the calibration of the TIME functions. TIME PICKUP settings of 00 also affect
INST functions.
Observe all applicable electrostatic discharge (ESD) precautions when handling
the relay assembly.
Summary of Contents for BE1-50B-230
Page 2: ......
Page 6: ...iv BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 8: ...vi BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 10: ...ii BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 18: ...1 8 BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 32: ...ii BE1 50 51B 230 234 Installation 9252000894 Rev D This page intentionally left blank...
Page 38: ...ii BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...
Page 50: ...5 12 BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...