9252000894 Rev D
BE1-50/51B-230/-234 General Information
1-1
SECTION 1
•
GENERAL INFORMATION
INTRODUCTION
BE1-50/51B-230 and BE1-50/51B-234 relays provide non-directional, single-phase or ground overcurrent
protection and are direct replacements for General Electric IAC66K relays. The BE1-50/51B-230 has a 5
ampere current sensing input. The BE1-50/51B-234 has a 1 ampere current sensing input. The BE1-
50/51B-230 and BE1-50/51B-234 relays are supplied as draw-out assemblies that plug directly into
existing cases for IAC66K relays. The draw-out assemblies are supplied with connection plugs, relay
covers, and adaptor plates for mounting the covers onto existing IAC66K cases.
BE1-50/51B-230 and BE1-50/51B-234 relays are self-powered, compatible with 50 or 60 Hz power
systems, and have three protection elements: one time overcurrent (51) element and two instantaneous
overcurrent (50) elements. The 51 element offers timing characteristic curves similar to those used by GE
IAC and ABB relays.
FEATURES
A wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
In addition, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B-230 and BE1-50/51B-234 overcurrent relays have the following standard features.
•
Independent time and instantaneous elements
•
A secure method to manually trip the breaker at the relay front panel
•
Direct reading front panel controls
•
Minimum pickup setting for safety during installation
•
Time characteristics extend to a pickup multiple of 40
•
Rugged draw-out construction with steel case
•
Gravity latching targets retain indication without power
•
Built-in accuracy eliminates internal adjustments
•
Minimum transient overreach
•
Field selectable characteristic curve selection similar to either GE IAC or ABB type curves
•
Field selectable instantaneous or integrating reset
•
Field selectable 50 or 60 Hz operation
•
Field selectable 0.0 or 0.1 second, fixed, instantaneous delay
Internal switches provide for selecting system-operating frequencies of 50 or 60 Hz, instantaneous
element delays of 0.0 or 0.1 second, characteristic curve group selection for either GE IAC or ABB type
curves, and instantaneous or integrating reset characteristics. Switch location and description is provided
in Section 2.
Advantages
BE1-50/51B-230 and BE1-50/51B-234 overcurrent relays have many advantages over other overcurrent
relays. The primary advantages are:
•
Time characteristics are defined by equations and graphs
•
Field selectable time characteristics
•
Very low burden extends the linear range of the CTs
•
Self powered from the sensed current
•
Continuous
automatic
calibration
BE1-50/51B-230 and BE1-50/51B-234 overcurrent relays may be tested without removing the relay from
the case. Shorting contacts are provided for all current inputs when the connection plugs or relay chassis
is removed from the relay case.
Summary of Contents for BE1-50B-230
Page 2: ......
Page 6: ...iv BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 8: ...vi BE1 50 51B 230 234 Introduction 9252000894 Rev D This page intentionally left blank...
Page 10: ...ii BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 18: ...1 8 BE1 50 51B 230 234 General Information 9252000894 Rev D This page intentionally left blank...
Page 32: ...ii BE1 50 51B 230 234 Installation 9252000894 Rev D This page intentionally left blank...
Page 38: ...ii BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...
Page 50: ...5 12 BE1 50 51B 230 234 Testing 9252000894 Rev D This page intentionally left blank...