Installation
POLARIS PROFESSIONAL
- für Zone 1/21
POLARIS Panel PC Professional 10,4" / 12,1" / 12,1" W
EN 44/68
Technical data subject to change.
04/2019
6.7.5
Fibre-optic port (optional)
For the fibre-optic transmission a fibre-optic converter is used inside the POLARIS and it
converts the Ethernet/IP to fibre-optic signals (Ethernet/IP Ex e connection is not required).
For transmission a converter of the same type is needed for the non-hazardous area. This
is included in the scope of supply.
Technical Data
Connection of the POLARIS
ST connector
External fibre-optic converter
Connection of the ST connector/RJ 45
plug
Power supply
external power pack
Data rate
100 MBit/s
Permissible ambient temperatures
Storage/transport
Operation
-20 °C bis +80 °C
0 °C bis +55 °C
Multi-mode
Converter
Range
Fibre type
Min. transmitting power
Min. sensitivity
Wave length
Plug connector
MS400161
up to 2 km
62.5/125 µm or 50/125 µm
19 dBm
31 dBm
1310 m
ST
Single-mode
Converter
Range
Fibre type
Min. transmitting power
Min. sensitivity
Wave length
Plug connector
MS400163
up to 15 km
9/125 µm
15 dBm
31 dBm
1310 m
ST
The POLARIS fibre-optic connection is approved for op pr. The following must be
observed when installing.
DANGER
There is a risk of fatal injury in an explosive atmosphere!
Protect the ST sockets from impact effects.
Make sure the plug on the fibre-optic cable is connected or closed before you put
the POLARIS into operation.
The fibre optic cable must laid with protection. (e.g. robust cabling, protective
tubes or cable channel)