Installation
POLARIS PROFESSIONAL
- für Zone 1/21
POLARIS Panel PC Professional 10,4" / 12,1" / 12,1" W
EN 34/68
Technical data subject to change.
04/2019
6.6.4
RS422 interface
Configuration RS422
Terminal Interface
Signal
Remarks
X17
X18
Termination
On/Off
Jumper between terminal X17 and
X18 for activation of the terminator
resistors
X19
Interface COM 1
TxD B (TxD+)
Transmission cable
Input
X20
Interface COM 1
TxD A (TxD-)
Transmission cableI
Input
X21
Interface COM 1
RxD B (RxD+) Receiving cable
Input
X22
Interface COM 1
RxD A (RxD-)
Receiving cable
Input
Connection PLC with RS422 interface to POLARIS.
Maximum length of the data line 1,000 m.
Setting of the terminal resistors at the start and end of the bus line is not necessary in
most cases due to internal EMC measures. Depending on local circumstances, the data
transmission may worsen in individual cases.
The appropriate pin assignment of the controller can be found in the manufacturer’s
interface description.
Under Os Windows 7 or 10 is only a point to point connection possible.