Manual 2100-592C
Page
30 of 69
21. STANDARD ORIFICE SIZING AND
HIGH ALTITUDE DERATE
This furnace is shipped with fixed gas orifices for use
with natural gas and sized for 1000 BTU/cubic foot
gas. Make sure actual gas input does not exceed rating
plate input. The orifices may need to changed to get
the correct gas input. Whether they need changed
or not depends on input and the gas heat value at
standard conditions and elevation. Consult the local
gas supplier for gas heat value and any special derating
requirements. See Section 20 for more information.
At higher altitudes, the density of the air is reduced.
Therefore, for proper combustion, the quantity of gas
burned in the furnace must also be reduced. This
is called derating. This unit must be derated when
installed at altitudes greater than 6,000' above sea
level. A high altitude pressure switch must also be
installed for operation above 6,000'. High altitude
pressure switch kit number 8620-189 is designed for
this application.
Table 7
Natural Gas Derate Capacities for All Models
W**G Rated
Input
Sea Level
1000
2000
3000
4000
5000
6000
7000
8000
9000
10,000
41,000
45,000
40,500
45,000
39,204
43,560
37,908
42,120
36,612
40,680
35,640
39,600
34,992
38,880
34,182
37,980
33,696
37,440
33,048
36,720
32,643
36,270
32,076
35,640
61,000
68,000
60,750
67,500
58,806
65,340
56,862
63,180
54,918
61,020
53,460
59,400
52,488
58,320
51,273
56,970
50,544
56,160
49,572
55,080
48,965
54,405
48,114
53,460
75,000
81,000
75,000
81,000
72,600
78,408
70,200
75,816
67,800
73,224
66,000
71,280
64,800
69,984
63,300
68,364
62,400
67,392
61,200
66,096
60,450
65,286
59,400
64,152
90,000
100,000
90,000
100,000
87,120
96,800
84,240
93,600
81,360
90,400
79,200
88,000
77,760
86,400
75,960
84,400
74,880
83,200
73,440
81,600
72,540
80,600
71,280
79,200
113,000
125,000
112,500
125,000
108,900
121,000
105,300
117,000
101,700
113,000
99,000
110,000
97,200
108,000
94,950
105,500
93,600
104,000
91,800
102,000
90,675
100,750
89,100
99,000
It is the installer’s responsibility to see that the
furnace input rate is adjusted properly. Derating
must be achieved by reducing the size of the main
burner orifices. Derating the furnace by adjusting the
manifold pressure lower than the range specified in
the Section 19, “Manifold Pressure Adjustment” is
considered to be an improper procedure.
Above 6,000' elevation orifice changes are required,
and capacity reductions are a function of altitude
impact and orifice change. Pressure switch change is
required above 6,000' elevation. For natural gas see
Altitude Table 7 below and Orifice Tables 8 and 8A on
following pages.
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...