35. PRESSURE SERVICE PORTS
High and low pressure service ports are installed on
all units so that the system operating pressures can be
observed.
36. DEHUMIDIFICATION CIRCUIT
The dehumidification circuit incorporates an
independent heat exchanger coil in the supply air
stream. This coil reheats the supply air after it passes
over the cooling coil without requiring the gas burner to
be used for reheat purposes. This results in very high
mechanical dehumidification capability from the air
conditioner on demand without using gas reheat.
The dehumidification refrigerant reheat circuit is
controlled by a three way valve directing the refrigerant
gas to the normal condenser during periods when
standard air conditioning is required. During periods of
time of low ambient temperature (approximately 65° to
75° outdoor) and high indoor humidity, a humidistat
senses the need for mechanical dehumidification. It
then energizes both the compressor circuit and the
three way valve, thus directing the hot refrigerant
discharge gas into a separate desuperheating
condenser circuit, which reheats the conditioned air
before it is delivered to the room. The refrigerant gas
is then routed from the desuperheating condenser to
the system condenser for further heat transfer. A small
orifice inserted between the reheat coil return line and
suction line will prevent liquid from accumulating in
the reheat coil when it is inactive. This drain does not
affect the normal operation of the system. A check
valve is located in the reheat oil return line. It has
a soft spring to hold the ball on the seat. This will
make the method of checking the ball freedom with a
magnet difficult. Refer to Figure 19 for the location
of the check valve and drain back capillary. When
the humidistat is satisfied, the system automatically
switches back to normal air conditioning mode and
either continues to operate or turns off based on the
signal from the wall thermostat. The result is separate
humidity control at minimum operating cost.
Air Conditioning Mode
Circuit Diagram
Dehumidification Mode
Circuit Diagram
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...