Manual 2100-592C
Page
21 of 69
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
16. WIRING – LOW VOLTAGE WIRING
Low Voltage Connection
These units use a 24-volt AC low voltage circuit.
The “R” terminal is the
hot
terminal and the “C”
terminal is
grounded
.
“G” terminal is the
fan input
.
“Y1” terminal is the
compressor input
.
“R” terminal is 24
VAC hot
.
“C” terminal is 24
VAC grounded
.
“A” terminal is the
ventilation input
. This terminal
energizes any factory or field installed vent option.
“2” terminal is the “L” input back to the thermostat if
compressor control module is tripped.
“3” terminal is the
dehumidification input
.
This energizes compressor, blower and 3-way
dehumidification valve.
“W1” terminal is the
heating input
.
230/208 Volt Units
All models are equipped with dual primary voltage
transformers. All equipment leaves the factory wired
on 240V tap. For 208V operation, reconnect from
240V to 208V tap. The acceptable operating voltage
range for the 240V and 208V taps are:
460 Volt Units
All models are equipped with single primary voltage
transformers and no rewiring is required.
FIGURE 10
Installation of Flexible Conduit
Direct Digital Controls (DDC)
For total and proper control using DDC, a total of 5
controlled outputs are required (4 if no ventilation is
installed).
LOW VOLTAGE CONNECTIONS FOR DDC CONTROL
Fan Only
Energize G
Cooling Mode
Energize G, Y1
Heating Mode
Energize W1
Ventilation
Energize G, A
Dehumidification
Energize 3
Tap
Range
240
253 – 206
208
220 – 187
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...