9. CLEARANCES
Minimum clearances, as specified in Table 2, must
be maintained from adjacent structures to provide
adequate fire protection, adequate combustion air, and
room for service personnel.
While minimum clearances are acceptable for safety
reasons, they may not allow adequate air circulation
around the unit for proper operation in the cooling
mode. Whenever possible, it is desirable to allow
additional clearance, especially around the condenser
inlet and discharge openings. DO NOT install the unit
in a location that will permit discharged air from the
condenser to recirculate to the condenser inlet.
TABLE 2
Minimum Installation Clearances
Outlet Duct
(from combustible materials)
1" first 3'
Vent Terminal
(from combustible materials)
* 17"
Condenser Inlet
20"
Top
See Figure 3
Burner Service
20"
Combustible Base (Wood or Class A,
B or C roof covering material)
0"
* See Figures 3 and 3A
FIGURE 7
Location of Vent Terminal in Shipping
WARNING
Clearances from combustible materials must
be maintained as specified. Failure to maintain
clearances could cause fire resulting in
property damage, injury, or death.
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...