Manual 2100-592C
Page
31 of 69
TABLE 8
Natural Gas Orifice Tables for Models
W24G, W30G and W36G
All other orifice sizes shown are available as individual items. See Orifice tables below for part numbers and number required.
Factory Standard
Input
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000' No
Changes Except
for BTU Content
6,001' to 8,000'
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001' to 10,000'
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
22500 BTU
Per Burner
700-749
2.75
2.70
2.60
750-799
2.70
2.60
2.50
800-849
2.60
2.50
2.45
850-899
2.50
2.45
2.35
900-949
2.45
2.35
(2.30)
950-999
2.35
(2.30)
2.25
1000-1049**
(2.30)
2.25
[2.20]
1050-1100
2.25
[2.20]
2.15
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
(2.30) is the standard factory-installed orifice size
[2.20] orifices are shipped with the unit for field-installed
optional 10% derate
Optional
10% Field
Converted Derate
Gas Heat* Value
BTU/Cu. Ft.
Up to 6,000 Feet No
Changes Except
for BTU Content
6,001' to 8,000'
Requires Pressure Switch
Change and Orifice
Change Based on BTU
Content
8,001' to 10,000'
Requires Pressure Switch
Change and Orifice Change
Based on BTU Content
20250 BTU
Per Burner
700-749
2.60
2.50
2.45
750-799
2.50
2.45
2.40
800-849
2.45
2.40
(2.30)
850-899
2.40
(2.30)
2.25
900-949
(2.30)
2.25
[2.20]
950-999
2.25
[2.20]
2.15
1000-1049**
[2.20]
2.15
2.10
1050-1100
2.15
2.15
2.10
Pressure Switch
Standard (.55)
Order 8620-189 High Altitude Pressure Switch Kit (.42)
[2.20] orifices are shipped with the unit for field-installed optional
10% input rate
(2.30) is the factory-installed orifice size for full rated
input
At standard conditions: 30.00 inches Mercury, 60F, saturated, .60 specific gravity.
All natural gas factory orifice sizing and standard input ratings based on nominal 1025 BTU/cu. ft. gas and sea level conditions
*
**
Bard Part No.
Orifice Size (mm)
Orifice Diameter
9010-092
2.10
0.0826
9010-088
2.15
0.0846
9010-087
2.20
0.0866
9010-086
2.25
0.0885
9010-082
2.30
0.0905
9010-085
2.35
0.0925
9010-079
2.40
0.0945
9010-084
2.45
0.0964
9010-093
2.50
0.0984
9010-094
2.60
0.1024
9010-095
2.70
0.1063
9010-096
2.75
0.1082
9010-097
2.80
0.1102
9010-098
2.90
0.1142
No. of Orifices Required Based
on Unit Input Rating
41,000 (2)
45,000 (2)
61,000 (3)
68,000 (3)
75,000 (3)
81,000 (4)
90,000 (4)
100,000 (4)
113,000 (5)
125,000 (5)
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...