Manual 2100-592C
Page
33 of 69
23. MEASURING AIR TEMPERATURE
RISE
Air temperature rise (supply air temperature minus
return air temperature) must be within allowable air
temperature rise range specified on furnace rating plate
and in Table 1.
Two thermometers with 1° resolution capable of reading
up to 200° F are needed. Check thermometers to
make sure they agree, or compensate accordingly.
Follow this procedure:
1. Open supply air registers and return air grilles.
Make sure the registers and grilles are free of
obstruction from rugs, carpets, drapes or furniture.
2. Set balancing dampers in supply duct system.
3. Check duct work for obstructions or leaks.
4. Make sure filters are clean and in place.
22. CONVERSION OF GAS INPUT BTUH
FROM HIGH TO LOW RATING
All the derated WG series units are produced with
maximum BTUH input orifices installed. To field
convert input, a change to main burner orifices is
required.
NOTE: No change to air orifices is necessary. A set of
low input orifices is shipped with every unit.
They are located in a bag behind the burner
door. Refer to the unit rating plate to confirm
the proper orifice size. Proper installation of
the orifices is detailed as follows:
A. Shut off electrical supply to the unit.
B. Shut off gas supply to the unit.
C. Remove burner access panel.
D. Disconnect gas valve from gas supply piping.
E. Disconnect the two wires from the gas valve.
F. Remove the manifold assembly so that orifices are
now accessible and remove orifices.
G. Apply a modest amount of pipe compound to the
new orifices and screw them into the manifold.
H. To assemble burner, reverse steps A through G.
5. Place one thermometer in supply air plenum
approximately 2’ from furnace. Locate
thermometer tip in center of plenum to ensure
proper temperature measurement.
6. Place second thermometer in return air
duct approximately 2’ from furnace. Locate
thermometer tip in center of duct to ensure proper
temperature measurement.
7. Set room thermostat on highest temperature
setting. Operate furnace 10 minutes. Record
supply air and return air temperatures.
8. Calculate air temperature rise by subtracting return
air temperature from supply air temperature.
• If air temperature rise is above the
temperature rise range on rating plate, furnace
is overfired or has insufficient airflow. Check
gas input following the instructions in Section
“Checking Gas Input Rate”. If air temperature
rise is still above temperature rise range
specified, more heating airflow is needed.
Check duct work and grilles to make sure all
are properly sized.
• If air temperature rise is below the
temperature rise range on rating plate, furnace
is underfired or has too much airflow. Check
gas input following the instructions in Section
“Checking Gas Input Rate”. If air temperature
rise is still below temperature rise range
specified, less heating airflow is needed.
Adjust dampers or grilles as needed.
• After making adjustments, check air
temperature rise to verify that resulting air
temperature rise is within allowable range.
If air temperature rise is still outside the
temperature rise range specified on rating
plate, check duct system design with a
qualified heating engineer. It may be
necessary to re-size the duct work. Recheck
air temperature rise after revising duct
systems.
9. Set room thermostat to desired setting.
10. Remove thermometers and seal duct work holes.
NOTE: Failure to seal holes could result in reduced
system performance.
WARNING
Failure to follow these instructions could create
a hazard resulting in property damage, bodily
injury, or death.
Summary of Contents for W24G2DA
Page 13: ...Manual 2100 592C Page 13 of 69 FIGURE 2A Mounting Instructions for W42G W48G and W60G...
Page 16: ...Manual 2100 592C Page 16 of 69 FIGURE 6 Common Wall Mounting Installations...
Page 26: ...Manual 2100 592C Page 26 of 69 FIGURE 12 Gas Pipe Connection W24G W36G W42G W60G...
Page 55: ...Manual 2100 592C Page 55 of 69 W24G2DA W48G2DA W60G2DA 230 208 60 1...
Page 57: ...Manual 2100 592C Page 57 of 69 W24G2DB W48G2DB W60G2DB 230 208 60 3...
Page 59: ...Manual 2100 592C Page 59 of 69 W24G2DC 460 60 3...
Page 61: ...Manual 2100 592C Page 61 of 69 W30G2DA W36G2DA W42G2DA 230 208 60 1...
Page 63: ...Manual 2100 592C Page 63 of 69 W30G2DB W36G2DB W42G2DB 230 208 60 3...
Page 65: ...Manual 2100 592C Page 65 of 69 W30G2DC W36G2DC W42G2DC 460 60 3...
Page 69: ...Manual 2100 592C Page 69 of 69 W48G2DC W60G2DC 460 60 3...