Action Rules
Supports simple logic, arithmetic and thresholding
Use for low complexity solutions
SMS text message Notifications
E-mail Notifications
Push data on conditions
Text Programming Language
ScriptBasic
Use when Action Rules cannot supply a solution
Scheduler
Time/calendar-based events
Astronomical clock
Data Logging
Cyclic Data/Event logging
E-mail log files
SMS Commanding
Read/Write Local Registers
Upload data to the cloud-based data service
Reboot controller
User Interface
—A simple user interface consists of an LCD screen and four LED indicators. Use the LCD to access system
status and setup, view user selectable events or data, and to bind and perform site surveys for Sure Cross radios. Configure
the user programmable LEDs to indicate the status of the DXM, processes, or equipment.
User programmable LCD
Binding Sure Cross radios
Conducting a Site Survey
Viewing sensor information
Viewing the system's status
User Defined LED indicators
1.3 System Overview for the DXM1500-B1
Banner's DXM Logic Controller integrates Banner's wireless radio, cellular connectivity, and local I/O to provide a platform for
the Industrial Internet of Things (IIoT).
Figure 3. DXM1500-B1 system overview
Connectivity
Cellular
Sure Cross Radios
Ethernet
USB
RS-485 Master
RS-485 Slave
RS-232
User Interface
LCD Screen
LED Indicators
I/O
Universal Inputs
Discrete Outputs
Courtesy Power
Isolated Inputs
Relay Outputs
Logic Controller
Action Rules
Programming Language
Scheduler
Push to the Cloud
Data Logging
SMS and Email
Table 1: Modbus registers for internal local registers (Modbus slave ID 199)
Local Registers
Type
Description
1–845
32-bit integer
Local data registers
846–849
32-bit integer
Reset, Constant, Timer
851–900
32-bit non-volatile integer
Data flash, non-volatile
901–1000
Reserved for internal use
1001–5000
Floating point
Floating point registers, local data registers
5001–7000
32-bit integer
Local data registers
7001–8000
32-bit non-volatile integer
Data flash, non-volatile
> 10000
Read only virtual registers, system-level data
Inputs/Outputs
—On-board universal and programmable I/O ports connect to local sensors, indicators, and control
equipment.
Sure Cross
®
DXM150 and 1500-Bx Wireless Controllers
www.bannerengineering.com - Tel: + 1 888 373 6767
7