Figure 232. Drag to Connect
The connection is made.
9. Double-click the iVu icon to open the Device window.
10. Select the desired modules or submodules from the Hardware catalog and drag them onto the Device overview tab
on the Device view tab.
The iVu device is configured.
Changing the Device IP Address
Use these instructions to change the IP address of the iVu device, using the Siemens TIA Portal (v13) software. Use these
instructions as a basis if you are using another controller (PLC).
1. Start the Siemens TIA Portal (v13) software.
2. Click Open existing project.
3. Select a project an open it.
4. Click Devices & networks after the project has been uploaded to go to Network view.
Figure 233. Network View
Network View displays.
5. Double-click on the iVu icon to open the Device view.
6. Click on the iVu icon in the graphic area of the Device view to open the Module properties window.
The module can now be configured.
7. Click Properties.
8. Click General.
9. Select PROFINET interface > Ethernet addresses.
Figure 234. Ethernet Addresses
10. Select Set IP address in the project.
iVu Plus TG and Color Gen2 Image Sensors