DP0041
MOUNTING
- Always mount the sensor supply unit (NivOil CU) outside the hazardous areas ("safe area").
Mount probes:
The routing of the connecting lines of the probes through the separation between the areas with category 1G requirements
and less hazard areas must be carried out in such a way that the degree of protection IP67 in accordance with EN 60529 is
ensured.
Oil probe (NivOil OP):
Install the sensor in such a way that the tip of the probe is positioned at the height of the desired alarm point.
The probe tube has three circumferential markings at a distance of 5cm, 10cm and 15cm from the probe tip (= switching point).
They are used to easily set the desired alarm point.
High level probe (NivOil HP):
Mount in the inlet chamber, the lateral hole must be at the height of the desired max. permissible accumulation level.
High level probe (NivOil HPS):
Mount the probe so that the lower edge of the ultrasonic fork is at the height of the desired max. permissible inflation level.
Sludge level probe (NivOil SP):
Mount the probe so that the lower edge of the ultrasound fork is approx. 2cm lower than the desired alarm point.
NON-EX ZONE
EX ZONE
Power
NivOil CU
HP / HPS
SP
OP
LEV
21-03-2023
M-531.01-EN-AI
OIL/LIGHT LIQUID
SEPARATOR MONITORING
NivOil - (translation)