Switching Counter – Auto Mode
On every rising edge of the input signal, the counter value
is increased (see Fig. 6-4).
If the counter value is less than the configured counter
limit, the counter state flag
not reached
is set. As soon as
the count value is greater than or equal to the configured
counter limit, the counter state flag
reached
is set. If the
count value is greater than the configured counter limit, the
count value is automatically reset (count value = one).
The count value can be reset at any time by a system
command (count value = zero).
Fig. 6-4: Switching counter – Auto Mode
6.3.3 Process Data
Object ID
Name
Description
Direction
0x0003 (3)
Switching Counter Limit not reached
Switching Counter Value < Limit
Input
0x0004 (4)
Switching Counter Limit reached
Switching Counter Value ≥ Limit
Input
0x0005 (5)
Switching Counter Limit exceeded
Switching Counter Value > Limit
Input
0x0006 (6)
Switching Counter Value
Switching Counter Value
Input
0x0007 (7)
Switching Counter Reset
Reset Switching Counter
Output
Tab. 6-14: Switching counter – process data
6
Secondary Device Functions (continued)
BOS R254K-UUI-LS10-S4
Photoelectric Sensors