www.balluff.com
61
english
6
Secondary Device Functions (continued)
6.11.3 Process Data
Object ID
Name
Description
Direction
0x0036 (54)
Inclination Deviation Value
1)
Value of the inclination deviation
Input
0x0037 (55)
Inclination Alarm Status
Inclination alarm status
Input
1)
Unit = ° (degree)
Tab. 6-52: Inclination and installation aid – Process data
6.11.4 ISDU
Name
Index
Subindex
Access
Length
Data Type Data Storage
Default
Inclination Alarm
Configuration
0x2151 (8529)
0
R/W
2 bytes
Yes
Inclination Alarm Enable
1
R/W
1 byte
BOOL
No
0x00 (0)
Inclination Alarm
Threshold
2
R/W
1 byte
UINT8
No
0x0A (10)
Inclination Alarm Status
0x2152 (8530)
0
R
2 bytes
n/a
Inclination Alarm
Teaching Status
1
R
1 byte
BOOL
n/a
–
Inclination Alarm Status
2
R
1 byte
BOOL
n/a
–
Reference Taught
Position
0x2153 (8531)
0
R
12 bytes
n/a
X Reference Value
1
R
4 bytes
FLOAT32
n/a
–
Y Reference Value
2
R
4 bytes
FLOAT32
n/a
–
Z Reference Value
3
R
4 bytes
FLOAT32
n/a
–
Inclination Deviation
Value
0x2154 (8532)
0
R
1 byte
UINT8
n/a
–
Tab. 6-53: Inclination and installation aid – ISDU
BOS R254K-UUI-LS10-S4
Photoelectric Sensors
Summary of Contents for BOS R254K-UUI-LS10-S4
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BOS R254K UUI LS10 S4 ...
Page 2: ...www balluff com ...
Page 3: ...BOS R254K UUI LS10 S4 Konfigurationsanleitung deutsch ...
Page 4: ...www balluff com ...
Page 88: ......
Page 89: ...BOS R254K UUI LS10 S4 Configuration Guide english ...
Page 90: ...www balluff com ...