BIS V-6111 CC-Link
Processor unit
42
english
Read times within the first block in dynamic mode
Data carrier with 32 bytes per block
No. of bytes
Read time [ms]
0 to 3
14
for each additional byte
3.5
0 to 31
112
Data carrier with 64 bytes per block
No. of bytes
Read time [ms]
0 to 3
14
for each additional byte
3.5
0 to 63
224
m = Highest address to read
Formula: t = (m + 1) * 3.5 ms
Example: Read 11 bytes starting at address 9. This means that the largest address to be read is
19. This yields 70 ms.
Note
Dynamic operation with BIS C: The times indicated apply after the data carrier has
been detected. Otherwise 45 ms must be added for powering up until the data carrier
is recognized. To achieve the read times specified in dynamic operation, the Tag Type
parameter has to be set to "BIS C 32 Byte" or "BIS C 64 Byte" on the respective
head.
The operating states of the identification system, the Profibus DP interface and the IO-Link
master are displayed using LEDs.
1
2
4
5
6
7
3
Figure 7: Function indicators
1
Ready device (RD)
5
Service/IO-Link
2
Ready (RD) CC-Link
6
COM R/W head
3
Display
7
RD R/W head
4
Error (ERR) CC-Link
7.3 Function
Indicator
Overview of
display elements
7
Device Function