1 Technical Description
1.1 I
NTRODUCTION
The OmniCarePLUS Multi-Exchange EVC comprises a network
of BS5839-9 compliant “local” systems, each “local” system can
control upto 64 outstations, and can be operated as a standalone
EVC system.
With the addition of the OmniCarePLUS network enabling the
installation of much larger systems, upto 126 Local Control
points (each controlling upto 64 outstations) can be networked
together making it possible to connect upto a maximum of 8064
outstations.
The benefit of OmniCarePLUS is the ability to communicate with
any outstation on any part of the network from a single “point”.
This sitewide control is via graphical touch screen(s) called
Network Control Stations (NCS).
The network can be either copper or fibre (either multimode or
single mode) but must be Fire Rated, Enhanced cable configured
as a loop. All site cables and connections, including internal
interfaces, chargers & batteries are fully monitored for faults.
Each local control point is supplied with a separate battery box.
Summary of Contents for OmniCarePLUS Multi-Exchange EVC
Page 6: ...OmniCarePLUS Multi Exchange EVC Installation Instructions vi OmniCarePLUS issue 1...
Page 18: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 8 OmniCarePLUS issue 1...
Page 34: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 24 OmniCarePLUS issue 1...
Page 42: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 32 OmniCarePLUS issue 1...
Page 44: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 34 OmniCarePLUS issue 1...
Page 46: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 36 OmniCarePLUS issue 1...
Page 48: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 38 OmniCarePLUS issue 1...
Page 53: ...OmniCarePLUS Multi Exchange EVC Installation Instructions OmniCarePLUS issue 1 43...
Page 54: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 44 OmniCarePLUS issue 1...