OmniCarePLUS Multi-Exchange EVC
Installation Instructions
10
OmniCarePLUS issue 1
2.3 R
ECOMMENDATIONS
FOR
"M
ASTER
S
TATION
" L
OCATION
To meet the requirements of BS5839-9 each local control panel is
considered a Master Station and as such their locations are defined
within BS5839-9.
N
OTE
: For full details please refer to BS5839-9.
For the purposes of BS5839-9 compliance, the Network Control
Stations are not defined as master stations.
Battery backup is supplied for each EVC Network Hub and is
sufficient to ensure the network remains operational in the case of
a local power failure. This meets the requirements of BS5839-9.
The Network Control Stations are outside of the scope of
BS5839-9, therefore consideration should be made to provide a
suitable alternative power source in the event of a local power
failure.
Summary of Contents for OmniCarePLUS Multi-Exchange EVC
Page 6: ...OmniCarePLUS Multi Exchange EVC Installation Instructions vi OmniCarePLUS issue 1...
Page 18: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 8 OmniCarePLUS issue 1...
Page 34: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 24 OmniCarePLUS issue 1...
Page 42: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 32 OmniCarePLUS issue 1...
Page 44: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 34 OmniCarePLUS issue 1...
Page 46: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 36 OmniCarePLUS issue 1...
Page 48: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 38 OmniCarePLUS issue 1...
Page 53: ...OmniCarePLUS Multi Exchange EVC Installation Instructions OmniCarePLUS issue 1 43...
Page 54: ...OmniCarePLUS Multi Exchange EVC Installation Instructions 44 OmniCarePLUS issue 1...