Care2
Installation Instructions
Care2 issue 9
81
7.6 M
AINTENANCE
M
ENU
S
TRUCTURE
Title
Description
Current Fault Status
View faults currently detected by the system,
"**" shows faults announced but not accepted.
Fault History Logs
View the stored fault log
Unmount SD Card (PIN)
Enables safe removal of the SD Card
Vendor Contact Details
View the Vendor Contact Details
Clear Device Assigns (PIN)
Removes the Device Assignments from the internal
modules (enables new / replacement modules to be fitted)
Force Sys Reset (PIN)
1
Force a System Reset
Force Con Reset (PIN)
2
Force a Console Reset
1
: "System Reset" - Master Console only: Resets Master Console & All Network Cards
2
: "Console Reset" - Slave & NEP Panels: performs a reset of the Local Console only
7.7 F
AULT
C
ODES
& B
ASIC
F
AULTFINDING
The faults that may be displayed by a console are explained in the
following sections:
7.7.1 “Battery Charger” - Local Console Fault
The battery charger has detected one of the following faults:
Battery Open Circuit, Battery Low Voltage, or Charger fault.
7.7.2 “Power Supply” - Local Console Fault
The Mains Supply is not connected and the Console is operating
on Batteries.
7.7.3 “System Restart xx” - Local Console Fault
There are five different System Restart faults:
POR - Power On Reset - Console has restarted due to Power loss
RI - Reset Instruction - Reset by code (Console or System Reset)
TO - Time Out - Processor watchdog caused reset
CM - Configuration Mistake - Internal Firmware Error
BOR - Brown Out Restart - Internal Power Supply fault.