Care2
Installation Instructions
Care2 issue 9
3
1.2.2 Network Expansion Panel
C2CBNEP (Black) & C2CSNEP (Stainless Steel) Network Expansion Panels
System self-monitoring
BS5839-9:2011 compliant
Power Supply
200V / 230V AC with integral batteries & charger
Power Consumption
75VA (plus approx 50mA per Remote Unit)
Front Panel Indicators
LCD Matrix Display & Rotary Encoder for System Control
LEDs: Power, Incoming Call, Refuge Areas Active, System
Healthy, Processor Restart, Common Fault, Processor Fault
Remote Signalling of Fault
Volt-free contact, closing/opening set at installation
Dimensions (W X H x D) 430mm x 310mm (7U) x 130mm
Bezel Dimensions (W x H) 470mm x 350mm
Weight
14Kg (with batteries)
Bezel Cutout (W x H x D) 440mm x 320mm x 135mm
Knockouts
20mm diameter x 23 in top only
Temp / Humidity Range
-10 to +30°C (storage and operating) / 95% Non Condensing
Internal Memory Card
SD (SDSC) 1GB Max
Figure 1.2 — Typical Care2 Network Expansion Panel
Each Network Expansion Panel can connect to 16 Outstations,
and upto 15 Network Expansion Panels (and one Master Console)
can be networked together to allow upto 256 Remote Units.
N
OTE
: Calls cannot be managed at Network Expansion Panels.