Care2
Installation Instructions
2
Care2 issue 9
1.2 T
ECHNICAL
S
PECIFICATIONS
1.2.1 Master & Slave Consoles
C2CB4 (Black) & C2CS4 (Stainless Steel) Consoles
System self-monitoring
BS5839-9:2011 compliant
Power Supply
200V / 230V AC with integral batteries & charger
Power Consumption
75VA (plus approx 50mA per Outstation)
Front Panel Indicators
LCD Matrix Display & Rotary Encoder for System Control
LEDs: Power, Incoming Call, Refuge Areas Active, System
Healthy, Processor Restart, Common Fault, Processor Fault
Remote Signalling of Fault
Volt-free contact, closing/opening set at installation
Dimensions (W X H x D) 430mm x 310mm (7U) x 130mm
Bezel Dimensions (W x H) 470mm x 350mm
Weight
14Kg (with batteries)
Bezel Cutout (W x H x D) 440mm x 320mm x 135mm
Knockouts
20mm diameter x 23 in top only
Security
Handset behind lockable door
Temp / Humidity Range
-10 to +30°C (storage and operating) / 95% Non Condensing
Internal Memory Card
SD (SDSC) 1GB Max
Figure 1.1 — Typical Care2 Console
The Care2 Console can be rack mounted using the C2CRM Rack
Mounting kit and is 7U high, although 2U must be left above to
allow for terminations.