Control Wiring 5-15
MN766
5.5.11 E-POT 3-Wire
Provides speed Increase and Decrease inputs to allow E-POT operation with 3 wire inputs. The opto inputs can be switches
as shown in Figure 5-15 or logic signals from another device.
Figure 5-15 E-POT 3-Wire Connection Diagram
User Analog Return
Analog Input 1
Analog Ref. Power +
1
2
3
4
5
6
7
J1
Analog Input 2+
Analog Input 2-
Analog Output 1
Analog Output 2
Enable
J2
Digital Output 1 + (Collector)
Digital Output 1 - (Emitter)
Digital Output 2 + (Collector)
Digital Output 2 - (Emitter)
See Figure 5-4 for
connection information.
Enable
Forward Start
Reverse Start
Stop
E-POT CMD Select
Accel/Decel
Increase
External Trip
Decrease
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
8
17
9
10
11
12
13
14
15
16
18
19
20
See recommended tightening torques in Table A-2.
*
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
J2-8
CLOSED allows normal control operation.
OPEN disables the control and the motor coasts to a stop.
J2-9
MOMENTARY CLOSED starts motor operation in the Forward direction.
J2-10
MOMENTARY CLOSED starts motor operation in the Reverse direction.
Note:
Closing both J2-9 and J2-10 at the same time will reset a fault.
J2-11
MOMENTARY OPEN motor decels to stop.
J2-12
CLOSED selects Level 1 Command Source parameter value.
OPEN selects E-POT.
J2-13
CLOSED selects ACC / DEC / S-ACC /S-DEC group 2.
OPEN selects ACC / DEC / S-ACC /S-DEC group 1.
J2-14
MOMENTARY CLOSED increases motor speed while contact is closed.
J2-15
MOMENTARY CLOSED decreases motor speed while contact is closed.
J2-16
Optional External Trip input (not required). If used, you must set Level 2 Drive Protect block, External Trip to “ON”.
CLOSED allows normal operation.
OPEN causes an External Trip to be received by the control (when programmed to “ON”).
Summary of Contents for VS1SD
Page 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Page 12: ...2 2 General Information MN766...
Page 16: ...3 4 Installing the Drive MN766...
Page 108: ...7 34 Parameter Descriptions MN766...
Page 114: ...8 6 Customizing Your Application MN766...
Page 128: ...9 14 Troubleshooting MN766...
Page 154: ...12 12 Monitor and RTC Description MN766...