C-2 CE Guidelines
MN766
C.3 EMC Installation Options
When installed for Class A or Class B operation, the control is compliant with EN55011 (1991)/ EN55022 (1994) for radiated
emissions as described.
C.4 Grounding for Wall Mounting (Class A)
also see Chapter 4
Top cover must be installed.
• A single-star point (earth) is required.
• The protective earth connection (PE) to the motor must be run inside the screened cable or conduit between the motor
and control and be connected to the protective earth terminal at the control.
• The internal/external AC supply fi lter must be permanently earthed.
• The signal/control cables must be screened.
C.5 Grounding for Enclosure Mounting (Class B)
also see Chapter 4
• The unit is installed for Class B operation when mounted inside an enclosure that has 10dB attenuation from 30
to 100MHz (typically the attenuation provided by a metal cabinet with no opening greater than 0.15m), using the
recommended AC supply fi lter and having met all cable requirements.
Note:
Radiated magnetic and electric fi elds inside the cubicle will be high and components installed inside must be
suffi ciently immune.
• The control, external fi lter and associated equipment are mounted onto a conducting, metal panel. Do not use enclosures
that use insulating mounting panels or undefi ned mounting structures. Cables between the control and motor must be
screened or in conduit and terminated at the control.
C.6 Use of CE Compliant Components
The following points should be considered:
• Using CE approved components will not guarantee a CE compliant system!
• The components used in the drive, installation methods used, materials selected for interconnection of components are
important.
• The installation methods, interconnection materials, shielding, fi ltering and earthing / grounding of the system as a whole
will determine CE compliance.
• The responsibility of CE mark compliance rests entirely with the party who offers the end system for sale (such as an OEM
or system integrator).
Summary of Contents for VS1SD
Page 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Page 12: ...2 2 General Information MN766...
Page 16: ...3 4 Installing the Drive MN766...
Page 108: ...7 34 Parameter Descriptions MN766...
Page 114: ...8 6 Customizing Your Application MN766...
Page 128: ...9 14 Troubleshooting MN766...
Page 154: ...12 12 Monitor and RTC Description MN766...