TABLE 7 – GENERAL PERFORMANCE SPECIFICATIONS
Notes: 1.
Catalog Nos. ID5202-CO, ID5203-CO: if a non-isolated signal is used, or if using 0 to ±25 Volts DC or 4 – 20 mA DC signal input,
install the ID5SI-1 Signal Isolator. Catalog Nos. ID5401-CO, ID5402-CO, ID5403-CO, ID5405-CO contain built-in signal isolation.
2.
Allows the
motor to operate up to two times the rated RPM. Constant motor horsepower will result when operating the drive in the “X2” mode above the
motor rated frequency.
3.
Dependent on motor performance.
4.
Do not operate the drive outside the specified AC line input voltage operating
range.
5.
Catalog Nos. ID5403-CO, ID5405-CO.
Description
Specification
Factory
Setting
208/230 Volt AC Line Input Voltage Operating Range (Volts AC)
208 (–15%) / 230 (+15%)
—
400/460 Volt AC Line Input Voltage Operating Range (Volts AC)
380 (–15%) – 460 (+15%)
—
Maximum Load (% Current Overload for 2 Minutes)
150
—
Carrier, Switching Frequency (kHz)
16, 8
—
Signal Following Input Voltage Range
1
(Volts DC)
Catalog Nos. ID5202-CO, ID5203-CO
0 – 5
—
Catalog Nos. ID5401-CO, ID5402-CO,
ID5403-CO, ID5405-CO
0 to ±25
0 to ±5
Signal Following Input Current Range
1
(mA DC)
4 – 20
—
Output Frequency Resolution (Bits, Hz)
10, .06
—
Minimum Speed Trimpot (MIN) Range (% Frequency Setting)
0 – 40
0
Maximum Speed Trimpot (MAX) Range (% Frequency Setting)
70 – 110
100
Acceleration Trimpot (ACC) and Deceleration Trimpot (DEC/B) Range (Seconds)
.3 – 20
1.5
Boost Trimpot (DEC/B) Range (50 Hz Only) (Volts/Hz)
0 – 30
5
Slip Compensation Trimpot (COMP) Range at Drive Rating (Volts/Hz)
0 – 3
1.5
Current Limit Trimpot (CL) Range (Amps AC)
Catalog No. ID5202-CO
4.0 – 12.5
10.7
Catalog No. ID5203-CO
5.5 – 17.0
14.4
Catalog No. ID5401-CO
1.3 – 3.8
3.2
Catalog No. ID5402-CO
2.1 – 6.2
5.3
Catalog No. ID5403-CO
3.0 – 8.5
7.4
Catalog No. ID5405-CO
5.0 – 15.5
13.3
Motor Frequency Setting (Hz) (Jumper J1)
50, 60
60
Output Frequency Multiplier (X1, X2) (Jumper J2)
2
1, 2
1
Minimum Operating Frequency at Motor (Hz)
1
—
Speed Range (Ratio)
60:1
—
Speed Regulation (30:1 Speed Range, 0 – Full Load) (% Base Speed)
3
2.5
—
Overload Protector Trip Time for Stalled Motor (Seconds)
6
—
AC Line Input Undervoltage/Overvoltage Trip Points for 208/230 Volt AC Line (±5%) (Volts AC)
4
151 – 282
—
AC Line Input Undervoltage/Overvoltage Trip Points for 400/460 Volt AC Line (±5%) (Volts AC)
4
302 – 567
—
Run/Fault Relay Output Contacts Rating5 (Amps at 30 Volts DC, 125 Volts AC, 250 Volts DC)
1, 0.5, 0.25
—
Operating Temperature Range (°C / °F)
0 – 45 / 32 – 113
—