INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 4
I-E96-411A
®
Cable Installation
Remove (pull off) the front cover of the termination module
before trying to install cables. Use the following procedures
when installing cables.
Figure 2-3. NIDO01 Cable Connections
T00528A
IMDSM05
IMLMM02
NIDO01
NKTM01
NKTU02/12
P3
P1
Table 2-1. NIDO01 Cable Applications
Nomenclature/
Description
Application
Connections
Maximum Length
m (ft.)
NKTU02 PVC termi-
nation cable
Connects the IDO module to
the master or slave module.
P1 of the IDO module to P3 of
the master or slave module.
61 (200)
NKTU12 non-PVC
termination cable
Connects the IDO module to
the master or slave module.
P1 of the IDO module to P3 of
the master or slave module.
61 (200)
NKTM01 ribbon com-
munication cable
Connects the IDO module to
the master or slave module.
P1 of the IDO module to P3 of
the master or slave module.
30 (100)
Standard 14 to 22
AWG wire
Connects field and power (18
AWG) wiring to the IDO mod-
ule.
Field or power source to the
IDO terminal strip.
N/A
CAUTION
Remove modules (slave, master, or termination) from their
assigned slots before installing a cable to that slot. Also,
remove stations from their housing before installing a cable to
that housing. Failure to do so could result in damage to the
module or station.
ATTENTION
Retirer les modules (asservi, maître ou carte de raccordement)
de leur position assignèe avant d'installer un câble à cette
position. Egalement, retirer les postes de commande de leur
boîtier avant d'installer un câble dans ce boîtier. Des dom-
mages au module ou au poste pourraient rèsulter d'un man-
quement à cette procèdure.